| Plan Review Notes For Permit 04090761 |
| Permit Number |
04090761 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW DISCONNECTING MEANS PER | | | 225.31, AND GROUNDING OF SAME PER | | | 250.32. | | | | | | 2} RECEPTACLES SHALL BE GFI PROTECTED | | | PER 210.8(A)(2). PLEASE INDICATE SAME | | | ON DRAWINGS. | | | | | | 3} PLEASE REMOVE THOSE PLANS AND | | | CALCULATIONS THAT DO NOT PERTAIN TO THE | | | SCOPE OF THIS APPLICATION. | | | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. SECTION | | | 104.2.1 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|