| Date |
Text |
| 2005-10-09 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE REAR PORCH IS SHOWING |
| | A J-BOX FOR POSSIBLE FUTURE FAN/LT. |
| | PLEASE SEE 210.70 LS 1015.8 WHICH |
| | REQUIRES A LT FIXTURE OF SOME SORT FOR |
| | MEANS OF EGRESS. |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR |
| | EACH PANEL ARE NOT COMPLETE AND ARE |
| | SHOWN WITH "0" LOAD ON EACH PANEL. |
| | PLEASE CORRECT, AND SHOW LOAD CALCS, AND |
| | LOAD ON EACH PANEL. |
| | 215.5,220 |
| | |
| | 3)NOTE: PLEASE SEE PLANS FOR ALL |
| | LOCATIONS WHICH INDICATE A PRE-WIRE FOR |
| | "SD'S". |
| | PLEASE SEE THIS SEEMS TO BE A MISPRINT |
| | AS "SD" IS FOR THE SMOKE DETECTORS AND |
| | THIS SHOULD BE "SP" FOR SPEAKER |
| | PRE-WIRE, IF INDEED THIS IS WHAT IS |
| | MEANT. |
| | |
| | 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| | BEING SHOWN CIRCUITED TO "A-20" , WHICH |
| | PANEL SCHEDULE SHOWS THIS AS THE SMALL |
| | APPLIANCE CIRCUIT. |
| | PLEASE SEE CIRCUIT A-20 IS ALSO BEING |
| | SHOWN ON PLANS FOR SMALL APPL. |
| | PLEASE SEE 210.52B1,210.11C1 WHICH DOES |
| | NOT PERMIT ANY OTHER DEVICES EXCEPT |
| | THOSE ALLOWED PER ABOVE. |
| | PLEASE ALSO SEE NOTES TO ELECTRICAL |
| | PLANS MENTIONS ONLY THOSE CIRCUITS |
| | LISTED TO BE "ARC-FAULT PROTECTED" , |
| | HOWEVER UNDER THE 2002 NEC 210.12, "ALL |
| | OUTLETS" BRANCH CIRCUITS" FOR BEDRMS ARE |
| | REQUIRED TO BE PROTECTED. |
| | PLEASE SEE NUMEROUS CIRCUITS AS NOTED DO |
| | NOT CORRELATE WITH PLANS OR PANEL |
| | SCHEDULES/ |
| | PLEASE SEE ARC FAULT PROTECTION LISTED |
| | FOR SM APPL, OVEN, A/C ETC, |
| | PLEASE CORRELATE ALL. |
| | |
| | 5)NOTE: PLEASE SEE BATH RM SHOWING |
| | CIRCUIT B-10, WHICH IS FOR ENTRY. THE |
| | BATH RM CIRCUITING SHALL BE PER |
| | 210.52D,210.11C3. IN EITHER CASE A |
| | RECEPT CIRCUIT MUST BE 20A AND #12. |
| | |
| | 6)NOTE: PLEASE SEE PANEL "B" IS BEING |
| | SHOWN AT TWO LOCATIONS ON PLANS??? |
| | PLEASE ADJUST. |
| | |
| | 7)NOTE: PLEASE KNOW, ALL "OPTIONAL" |
| | ITEMS SHALL BE SHOWN AS INSTALLED OR NOT |
| | INSTALLED IF NOT REQUIRED. |
| | OPTIONS MAY BE SHOWN ON ORIGINAL PLANS |
| | FOR PERMITTING, HOWEVER ALL |
| | OPTIONS/REVISIONS ARE TO BE SUBMITTED |
| | FOR REVIEW BEFORE ROUGH ELECTRICAL |
| | INSPECTION. |
| | |
| | 8)NOTE: PLEASE SEE NOTES PERTAINING TO |
| | AIC RATINGS OF MAINS TO BE USED. |
| | PLEASE CLARIFY NOTE, AS IT DOES NOT SEEM |
| | TO CONTAIN INFORMATION FOR LENGTHS |
| | BETWEEN 70-80 FT.??? |
| | PLEASE ADJUST. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |