| Plan Review Notes For Permit 04090582 |
| Permit Number |
04090582 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-26 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. THE ENERGY CODE FORM HAS TO BE | | | SIGNED BY THE OWNER/AGENT. | | | | | | 2.THERE ARE NO PRODUCT APPROVALS FOR | | | THE CASEMENT WINDOWS SHOWN ON THE PLANS. | | | | | | 3. THERE ARE PRODUCT APPROVALS FOR | | | THERMA-TRU DOORS THAT REQUIRE STORM | | | PANELS. | | | | | | 4. THE FIXED WINDOWS ARE "SMALL MISSLE | | | IMPACT". WHEN INSTALLED UNDER 30' THEY | | | REQUIRE STORM PANELS.NO STORM PANEL | | | INFORMATION SUBMITTED. | | | | | | 5. ADDITIONAL FEES ARE DUE BEFORE | | | PERMITCAN BE ISSUED INCLUDING APPROACH | | | FEE. | | | | | | 6. NO GLASS BLOCK SHOWN ON PLANS BUT | | | PRODUCT APPROVAL SUBMITTED. REMOVE ALL | | | PRODUCT APPROVALS FOR ITEMS NOT ON PLANS | | | | | | 7. A NOTICE OF COMMENCEMENT MUST BE | | | FILED AT THE COUNTY CLERK OFFICE & | | | SUBMITTED BEFORE A PERMIT CAN BE ISSUED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|