| Plan Review Notes For Permit 04090575 |
| Permit Number |
04090575 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | BUILDING REVIEW COMMENTS: | | | EXTENSION OF REAR PORCH WAS APPROVED, | | | BUT THE FOLLOWING ITEMS NEED TO BE | | | REVISED AS REQUIRED: | | | 1- BBQ SPECS SAY "DO NOT INSTALL A GRILL | | | BELOW OVERHEAD UNPROTECTED COMBUSTIBLE | | | CONSTRUCTION" AND "DO NOT LOCATE THE | | | GRILL IN A BUILDING, GARAGE OR OTHER | | | ENCLOSED AREA".PROVIDE MANUFACTURER | | | SPECS CLARIFYING THAT BBQ WILL BE OK TO | | | INSTALL IN PORCH. | | | | | | 2- REVISE ROOF FRAMING PLAN. TRUSS | | | BEARING ELEVATIONS NOTED AT ENTRY PORCH | | | ARE INCORRECT. | | | | | | 3- DETAIL M/6 AND ROOF FRAMING PLAN | | | DON'T MATCH. REVISE: A) TYPE OF BEAM. | | | B) NEED WOOD TO WOOD CONNECTOR. A1 | | | CONNECTOR DON'T WORK FOR WOOD FRAMED BOX | | | C) ROOF FRAMING LAYOUT AND DETAIL DON'T | | | MATCH. SEE FRAMING AND OVERFRAMING SHOWN | | | ON ROOF PLAN. | | | D) SPECIFY FIREBLOCKING ON DETAIL M/6. | | | SECTION 2305.1 FBC 2001. | | | E) THERE ARE 2 DIFFERENT ATTIC VENTS | | | SPECS. CLARIFY WHICH ONE APPLY. | | | F) SPECIFY METAL ANCHORS. "APPROVED | | | METAL ANCHORS ARE NOT SUFFICIENT INFO. | | | SEC. 104.2.1 CITY AMENDMENTS TO FBC 2001 |
|