2004-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A4 0F 7 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN.
 A) CABANA BATH SHOWS A SHOWER ON THE
 RISER DIAGRAM THAT IS NOT ON THE FLOOR
 PLAN. SECTION 104.2.1
 B) MASTER BATH SHOWS THE BIDET TO THE
 RIGHT OF THE W/C ON THE FLOOR PLAN, NOT
 BETWEEN THE W/C AND THE LAV AS SHOWN ON
 THE RISER DIAGRAM. SECTION 104.2.1
 C) THE WASH MACHINE REQUIRES A STAND-
 PIPE. SECTION 1002.1 & 802.4. - ALSO THE
 WASH MACHINE CLEANOUT SHALL BE 4' ABOVE
 THE FLOOR FOR ACCESS. SECTION 708.10.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]