| 2004-10-26 00:00:00 | CHECKLIST: |
| | 1-STORM SHUTTERS NOTE ON DWG A1 CALLS |
| | FOR SHUTTERS ON ALL OPENINGS & IMPACT |
| | GLAZING FOR ENTRY DOOR. PRODUCT APPRO- |
| | VALS SUBMITTED ARE FOR IMPACT GLAZING |
| | ON DOORS/WINDOWS AND ENTRY DOORS NEED |
| | SHUTTERS. CLARIFY AND REVISE AS REQ'D. |
| | **NOTE: PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS IF USED. |
| | 2-DRAWING A3: A)ROOF LOADS CHART & NOTE |
| | ABOVE ROOF FRAMING PLAN LETTERING ARE |
| | CONTRADICTING EACH OTHER. REVISE AS |
| | REQUIRED & SPECIFY 30PSF OR 10PSF LIVE |
| | LOAD AS REQUIRED BY TABLE 1604.1 FBC. |
| | B)ROOF SHEATHING NOTE: ZONE 3 ISN'T ONLY |
| | AT ALL 4 CORNERS OF ROOF. ZONE 3 ARE |
| | ALL CORNERS THROUGHOUT ENTIRE ROOF. |
| | REVISE AS REQUIRED. SEC. 104.2.1.2 OF |
| | CITY AMENDMENTS TO FBC 2001. |
| | C)KEY DETAILS SO THEY MATCH DETAILS ON |
| | DRAWING A6. REVISE AS REQUIRED. |
| | 3-OWNER/AGENT TO SIGN AND DATE THE |
| | ENERGY CALCULATIONS (BOTH COPIES). |
| | 4-PROVIDE BBQ UL LISTING AND SPECS. |
| | SEC. 2808 FBC 2001. |
| | 5-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A)FIXED WINDOWS FOR |
| | LARGE MISSILE IMPACT, NOT FOR SMALL |
| | MISSILE IMPACT. SEC. 1606.1.4 FBC 2001 |
| | B)ENTRY DOOR WITH MISSILE IMPACT GLAZING |
| | AS SPECIFIED ON PLANS. |
| | 6-PROVIDE COMPLETE DETAIL THAT SHOWS HOW |
| | ARE ENTRY PORCH TRUSS GIRDERS ATTACHED |
| | TO MASONRY WALL. DETAIL C/6 DO NOT |
| | MATCH SUCH CONDITION. REVISE DETAIL. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 7-PROVIDE COMPLETE FRAMING SECTION |
| | DETAIL AT ENTRY PORCH TO CLARIFY HOW |
| | IS PORCH SPECIFIED TO BE BUILT. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 8-MULLION PRODUCT APPROVAL: CLEARLY |
| | MARK ALL COMPONENTS TO BE USED ON THIS |
| | PROJECT ACCORDING TO THE SPAN AND SIZE |
| | OF MULLIONS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 9-DETAIL G/6: SPECIFY ALL FASTENERS. |
| | HOW ARE 2X4'S FASTENED, ETC. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001` |
| | 10-SHEET A7: CROSS SECTIONS DWGS FOR THE |
| | BEAMS AND LINTELS NEED THE ENGINEER'S |
| | ORIGINAL SIGNATURE, DATE AND SEAL AS |
| | REQUIRED BY CHAPTER 471 FL STATUTES. |
| | **ALSO, DRAWINGS ARE NOT LEGIBLE. |
| | 11-OWES $2138.98 FOR UPDATED VALUE AND |
| | UNPAID BALANCE AT TIME OF APPLICATION. |
| | 12-PLEASE, PROVIDE ONLY THE DETAILS THAT |
| | APPLY TO THIS PROJECT TO EXPEDITE THE |
| | REVIEW PROCESS AND AVOID CONFLICTS. |
| | |