| Date |
Text |
| 2004-10-05 00:00:00 | *********** UNSAT ************** |
| | |
| | ***PLEASE ALSO SEE NOTES UNDER 04070719 |
| | PERMIT FOR FOUNDATION SHOULD NOT HAVE |
| | BEEN ISSUED DUE TO VIOLATIONS UNDER |
| | FS 471.023 AND FAC 61G15-23.002 |
| | THIS WAS NOTED ON PREVIOUS REVIEW AS |
| | BEING REQUIRED FOR ALL SHEETS AND ALL |
| | TRADES WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER REVIEWERS. *** |
| | PERMIT/PLANS FOR 04070719 WILL BE PLACED |
| | ON HOLD. |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCK WHICH IS REQUIRED UNDER FS 471.023 |
| | ONE SET OF PLANS WILL NOW BE RETAINED |
| | FOR POSSIBLE REVIEW BY THE FBPE'S FOR |
| | ABOVE. |
| | |
| | 2)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS |
| | REVIEW. TELCO PANEL STILL APPEARS TO |
| | POSSIBLY HAVING TWO SERVICES FEEEDING |
| | THIS EQUIPMENT?? |
| | |
| | 3)NOTE: PLEASE CLARIFY TRANSFER AT |
| | TELCO PANEL. RISER SHOWS RECEPT/EM POWER |
| | BACK TO FEED EQUIPMENT IN THE EVENT OF A |
| | POWER FAILURE, PLEASE CLARIFY THIS CONN |
| | -ECTION SHOWN. IS THIS A TRANSFER SWITCH |
| | ? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |