2004-10-05 00:00:00*********** UNSAT **************
  
 ***PLEASE ALSO SEE NOTES UNDER 04070719
 PERMIT FOR FOUNDATION SHOULD NOT HAVE
 BEEN ISSUED DUE TO VIOLATIONS UNDER
 FS 471.023 AND FAC 61G15-23.002
 THIS WAS NOTED ON PREVIOUS REVIEW AS
 BEING REQUIRED FOR ALL SHEETS AND ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS. ***
 PERMIT/PLANS FOR 04070719 WILL BE PLACED
 ON HOLD.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK WHICH IS REQUIRED UNDER FS 471.023
 ONE SET OF PLANS WILL NOW BE RETAINED
 FOR POSSIBLE REVIEW BY THE FBPE'S FOR
 ABOVE.
  
 2)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS
 REVIEW. TELCO PANEL STILL APPEARS TO
 POSSIBLY HAVING TWO SERVICES FEEEDING
 THIS EQUIPMENT??
  
 3)NOTE: PLEASE CLARIFY TRANSFER AT
 TELCO PANEL. RISER SHOWS RECEPT/EM POWER
 BACK TO FEED EQUIPMENT IN THE EVENT OF A
 POWER FAILURE, PLEASE CLARIFY THIS CONN
 -ECTION SHOWN. IS THIS A TRANSFER SWITCH
 ?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  