| Plan Review Notes For Permit 04090541 |
| Permit Number |
04090541 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P-1 FULL OPEN VALVES SHALL BE | | | INSTALLED ON THE TOP OF EVERY WATER | | | DOWN-FEED PIPE. SECTION 606.1(4). | | | 2) FROM PREVIOUS REVIEW: SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH THE FOLLOWING: | | | 11-4.16.2 CLEAR FLOOR SPACE | | | 11-4.16.3 HEIGHT | | | 11-4.16.4 GRAB BARS | | | 11-4.16.5 FLUSH CONTROLS | | | 11-4.19.2 HEIGHT & CLEARANCES | | | 11-4.19.4 EXPOSED PIPES AND SURFACES | | | 11-4.19.5 FAUCETS | | | WATER CLOSET SHALL BE 18" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE. FIG. | | | 28 | | | LAV SHALL BE MINIMUM OF 15" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE TO BE | | | CENTERED ON THE 30" MEASURMENT OF THE | | | CLEAR FLOOR SPACE. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|