2004-10-05 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS PME ARE CONTAIN
 A "RUBBERSTAMP" FOR THE REQUIRED
 SIGNATURE OF THE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025. THIS IS REQUIRED
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE 250.24, 250.6, AN
 EQUIPMENT GROUNDING CONDUCTOR IS NOT TO
 BE INSTALLED AFTER METER AND BEFORE THE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE VERIFY IF CWP IS "METAL/
 COPPER, IF SO, PLEASE ALSO INCLUDE AS
 PART IF THE GROUDING ELECTRODE SYSTEM.
  
 4)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED IN TITLE BLOCK.
 THIS HAS BEEN REQUESTED ON PREVIOUS
 REVIEWS UNDER OTHER PERMITS.
 PLEASE ALSO SEE FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  