| Plan Review Notes For Permit 04090486 |
| Permit Number |
04090486 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-01-04 00:00:00 | FIRE REVIEW FAILED | | | | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE UL | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENTS | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL APPROVAL OF THE FIRE ALARM | | | SYSTEM. | | | | | | 3) FIRE ALARM CIRCUITS SHALL BE CLASS A, | | | STYLE D NOT CLASS B, STYLE Y OR 4. | | | | | | 4) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL CAUSE AN ALARM NOT A SUPERVISORY | | | SIGNAL. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|