| Plan Review Notes For Permit 04090472 |
| Permit Number |
04090472 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-24 00:00:00 | ********* PROVISO/ REVISION ********* | | | | | | 1)NOTE: PLEASE SEE PANEL/METER ETC IS | | | SHOWN AS 200A WITH A LOAD CALCULATION | | | SHOWING 201A LOAD. | | | PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | LOAD SHOWN IS FOR CONNECTED LOAD AT THIS | | | TIME. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS AFTER FIRST MEANS | | | OF DISCONNECT/TRANSFORMERS ETC. | | | 250.24,250.110,250.122 AND 250.30 | | | | | | REVISE AND SUBMIT BEFORE ROUGH ALONG | | | WITH ANY OTHER REVISIONS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|