Plan Review Notes
Plan Review Notes For Permit 04090472
Permit Number 04090472
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-24 00:00:00********* PROVISO/ REVISION *********
  
 1)NOTE: PLEASE SEE PANEL/METER ETC IS
 SHOWN AS 200A WITH A LOAD CALCULATION
 SHOWING 201A LOAD.
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 LOAD SHOWN IS FOR CONNECTED LOAD AT THIS
 TIME.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER FIRST MEANS
 OF DISCONNECT/TRANSFORMERS ETC.
 250.24,250.110,250.122 AND 250.30
  
 REVISE AND SUBMIT BEFORE ROUGH ALONG
 WITH ANY OTHER REVISIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]