2004-09-23 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SUBMIT FOR MAIN DISC ALSO.
  
 2)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 WINDOW RECEPTS> (ADVERTISEMENT) ETC.
  
 3)NOTE: PLEASE SEE IF THERE IS A MAIN '
 DISCONNECT ON THE LINE SIDE OF MAIN
 SHOWN, PLEASE SEE 250.24 FOR EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED.
  
 4)NOTE: PLEASE PROVIDE CONDUCTOR SIZES
 FROM WIREWAY TO METER/ MAIN. CONDUIT?
 215.5
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS, INCLUDING EM/EXT LTS. PLEASE
 ALSO SEE 700.12E
  
 6)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL INFORMATION REQUIRED ON TITLE BLOCK
 FOR ARCH/ARCH FIRM.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 CERTIFICATE OF AUTHRIZATION # REQUIRED
 FOR FIRM.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  