Plan Review Notes For Permit 04090400
Permit Number 04090400
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-10 00:00:00PERMIT 04090400
 BLDG # 34
 4740 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026