| Plan Review Notes For Permit 04090386 |
| Permit Number |
04090386 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-22 00:00:00 | DENIED:TYPE II BUILDING #25 | | | 1.PER 2001 FBC(M) 601.4 EXCEPTION #2 | | | & 3, RETURN TRANSFER GRILLES SHALL BE | | | SIZED AS FOLLOWS: | | | RETURN TRANSFER - 50 SQ INCHES OF FREE | | | AREA TO 100 CFM OF SUPPLY AIR TO THAT | | | AREA.ALL SUPPLY AIR INTO THE MASTER | | | SUITE SHALL BE INCLUDED FOR PROPER | | | SIZING. | | | THE FOLLOWING UNITS ARE NOT SIZED | | | PROPERLY - A-1 (DWG AC-U1), A-1LS (DWG | | | AC-U4), B-2 (AC-5). | | | | | | 2.PLEASE NOTE, THE TOILET EXHAUST | | | TERMINATION SHALL BE SCREENDED IN | | | ACCORDANCE WITH 2001 FBC(M) 401.6. | | | (DRYER EXHAUST NON-SCREENED) | | | | | | 3.PLAN SHEET PD-1 CONDENSATE RISER, | | | CONDENSATE SHALL TERMINATE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|