2004-10-21 00:00:00DENIED:
 1.PER 2001 FBC(M) 601.4 EXCEPTION #2
 & 3 TRANSFER GRILLES SHALL BE SIZED AS
 FOLLOWS:
 RETURN TRANSFER - 50 SQ INCHES OF FREE
 AREA TO 100 CFM OF SUPPLY AIR TO THAT
 AREA.ALL SUPPLY AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR PROPER
 SIZING.
 THE FOLLOWING UNITS ARE NOT SIZED
 PROPERLY - B2 (DWG AC-U5), C-3S (DWG
 AC-U10), C3-L (AC-U11), C-3LS (AC-U12)
  
 2.PLEASE NOTE, THE TOILET EXHAUST
 TERMINATION SHALL BE SCREENED PER
 2001 FBC(M) 401.6. (DRYER EXHAUST SHALL
 BE NON-SCREENED)
  
 3.CONDENSATE RISER INDICATED ON THE
 PLUMBING PLANS, CONDENSATE SHALL
 TERMINATE A MINIMUM OF 12" AWAY FROM THE
 BUILDING STRUCTURE.
  