| Plan Review Notes For Permit 04090384 |
| Permit Number |
04090384 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-21 00:00:00 | DENIED: | | | 1.PER 2001 FBC(M) 601.4 EXCEPTION #2 | | | & 3 TRANSFER GRILLES SHALL BE SIZED AS | | | FOLLOWS: | | | RETURN TRANSFER - 50 SQ INCHES OF FREE | | | AREA TO 100 CFM OF SUPPLY AIR TO THAT | | | AREA.ALL SUPPLY AIR INTO THE MASTER | | | SUITE IS TO BE INCLUDED FOR PROPER | | | SIZING. | | | THE FOLLOWING UNITS ARE NOT SIZED | | | PROPERLY - B2 (DWG AC-U5), C-3S (DWG | | | AC-U10), C3-L (AC-U11), C-3LS (AC-U12) | | | | | | 2.PLEASE NOTE, THE TOILET EXHAUST | | | TERMINATION SHALL BE SCREENED PER | | | 2001 FBC(M) 401.6. (DRYER EXHAUST SHALL | | | BE NON-SCREENED) | | | | | | 3.CONDENSATE RISER INDICATED ON THE | | | PLUMBING PLANS, CONDENSATE SHALL | | | TERMINATE A MINIMUM OF 12" AWAY FROM THE | | | BUILDING STRUCTURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|