| 2005-02-15 00:00:00 | BUILDING PLAN REVIEW |
| | |
| | PORTOFINO PHASE II |
| | |
| | PERMIT: 04090383 |
| | ADD: MASTER BLDG TYPE I |
| | CONT:EPOCH PROPERTIES |
| | TEL: (561)723-0152 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMMENT #4 FROM THE PREVIOUS REVIEW, |
| | SHEET A-DT4 DETAIL "J", PLANS HAVE A |
| | HIGH VALUE OF 1450 SEE 2005 CATALOG |
| | VALUE OF 1225. |
| | |
| | 2) COMMENT #6 FROM THE PREVIOUS REVIEW, |
| | WITH THE HURRICANE PREPAREDNESS PLAN, |
| | REVISE: |
| | A) AMOUNT OF ON SITE STAFF |
| | B) NO RESIDENCE TO HELP |
| | C) PROVIDE LABOR FORCE CONTRACT |
| | D) START ISSUANCE OF PLAN AT THE |
| | HURRICANE WATCH NOT WARNING |
| | E) SHUTTERS TO BE DOWN AS SOON AFTER |
| | THE STORM AS RESONABLY POSSIBLE. |
| | |
| | 3) COMMENT #7 FROM THE PREVIOUS REVIEW, |
| | DEALS WITH THE SOILS REPORTS: |
| | 3A) ONLY 1 SIGNED & SEALED COPY OF THE |
| | REPORT WAS SUBMITTED, (3)SIGNED & SEALED |
| | |
| | REPORTS ARE REQUIRED , RESIDENT |
| | INPSECTOR PROGRAM. |
| | 3B) THE ENGINEERING LETTER DATED |
| | 12/15/04 FROM PSI ALSO IS REQUIRED TO BE |
| | |
| | SIGNED AND SEALED. AGAIN (3) ORIGINAL |
| | SIGNATURES SIGNED & SEALED. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS4) |
| | |
| | 4) COMMENT #9 FROM THE PREVIOUS REVIW, |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) STORM SHUTTERS |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) COMMENT #10 FROM THE PREVIOUS REVIEW, |
| | DEEALS WITH THE MINIMUM DEPTH OF THE |
| | FOUNDATION, THE EXTERIOR GYPSUM BOARD |
| | IS TO STOP 8" FROM GRADE SEE (2506) AND |
| | THE FOUNDATION IS TO BE A MINIMUM OF 12" |
| | BELOW GRADE, YOUR GEO REPORT RECOMENDS |
| | 16", THE 2 COMBINED EQUAL A DEPTH OF 24" |
| | TO THE TOP OF SLAB. S-D1.1 INDICATES |
| | THIS ON THE DETAILS BUT THE FOUNDATION |
| | SHEET WAS NEVER CHANGED TO MATCH THE NEW |
| | DETAILS, SEE FOUNDATION WF-16A & WF-24A |
| | ON SHEET S-D4. |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |