Plan Review Notes
Plan Review Notes For Permit 04090383
Permit Number 04090383
Review Stop B
Sequence Number 2
Notes
Date Text
2005-01-19 00:00:00PORTOFINO PHASE II LAND, LTD
  
 BUILDING TYPE I
  
 BUILDING PLAN REVIEW
  
 PERMIT: 04090383BLDG# 22
 ADD: 4650 PORTOFINO WAY
  
 PERMIT: 04090384BLDG# 23
 ADD: 4635 PORTOFINO WAY
  
  
 CONT:EPOCH PROPERTIES, INC.
 TEL: (407)718-8932
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 AS DISCUSSED EARLIER, PLANS ARE NOW IN
 FOR PLAN REVIEW, NOT FOR PERMIT.
 CONTRACTOR TO INDICATE IF PLAN REVIEW IS
 TO BE CONVERTED INTO A "MASTER" OR IF
 INDIVIDUAL BUILDING PERMITS WITHWITH
 (3) SETS OF PLANS FOR EACH BUILDING
 SHALL BE SUBMITTED.
  
 SINCE THE PLANS ARE BEING SUBMITTED AS A
 PLAN REVIEW, NEW PERMIT APPLICATIONS
 SHALL BE SUBMITTED BY THE CONTRACTOR .
 THESE NEW PERMIT APPLICATIONS ARE TO
 REFLECT THE BUILDING NUMBER AND
 APPROPRIATE ADDRESS ON PORTOFINO WAY.
 NO PERMITSOR PLAN REVIEWS ARE TO
 REFLECT A MILITARY TRAIL ADDRESS. PLEASE
  
 CORRECT THE PLAN REVIEW APPLICATIONS
 WITH THE SITE ADDRESS AND THE CORRECT
 PROPERTYCONTROL NUMBER.SITE ADDRESS
 SHALL BE 4600 PORTOFINO WAY, THE SAME AS
 THE CLUBHOUSE.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) COMMENT # 3 FROM THE PREVIOUS
 REVIEW,
 DEELS WITH SHEET A-U13 DETAILS INDICATE
 THE USE OF SEMCO STRAPS, DESIGNER HAS
 CHANGED THE STRAP TO USP TAPL-14 BUT THE
 VALUES TAKEN ARE HIGHER THAN ALLOWED IN
 THE 2005 USP CATALOG.1609.4.3 LOAD
 REDUCTIONS, STEEL INCREASES CA NOT BE
 TAKEN.
  
 4) COMMENT # 5 FROM THE PREVIOUS
 REVIEW,
 SHEET A-T1.3 / A-U13,
 USP- RT-16 HIGH VALUE
 USP- RT-24 NOT IN CATOLOG
 USP DTC IS A OLD REFRENCE, CURRENT
 STOCK
 NUMBER IS TR-2, PROVIDE LOADS TO BE
 RESISTED SEE FOOTNOTES 2 & 3.
 USP- RT-24 NOT IN CATOLOG
 PROVIDE CURRENT LISTINGS FOR PRODUCTS
 LISTED ABOVE.
  
 5) COMMENT # 6 FROM THE PREVIOUS REVIEW
  
 DEALS WITH FIRE SPRINKLER PLANS
 REQUIRED. ATTACH THE FIRE SPRINKLER
 PLANS TO THE BUILDING SETS OF PLANS, TO
  
 HAVE A COMPLETE SUBMITTAL PACKAGE.
  
 6) COMMENT # 8 FROM THE PREVIOUS
 REVIEW,
 DEALS WITH HURRICANE SHUTTERS ON THE
 FIRST FLOOR. BUILDING OFFICAL NEIL
 MELICK HAS CHANGED THE REQUIREMENTS FOR
 LARGE PROJECTS SINCE THE LAST
 HURRICANES. PRESENTLY HE ISN'T
 ACCEPTING
 ANYTHING ON THE FIRST FLOOR FOR WINDOW
 OR DOOR PROTECTION EXCEPT FOR LARGE
 MISSLE IMPACT WINDOWS AND DOORS, AS HAS
 BEEN THE POLICY FOR THE 2ND AND 3RD
 FLOORS.
  
 7)COMMENT # 10 FROM THE PREVIOUS REVIEW,
 THE SOILS REPORTS TO BE SUBMITTED SHALL
 HAVE ORIGINAL SIGNNATURE & SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) COMMENT # 11 FROM THE PEVIOUS
 REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) COMMENT # 12 FROM THE PREVIOUS
 REVIEW
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRONT DOOR REPORT- MASONITE REPORT
 IS ILLEGIBLE PROVIDE CLEAR COPIES,
 NO POSITIVE OR NEGATIVE PRESSURES
 INDICATED ON REPORT.
 B) CLOSPAY GARAGE DOOR- MISSING THE
 FLORIDA PRODUCT APPROVAL COVERSHEET
 C) ROOFING ASSEMBLIES
 1) INDICATE THE METHOD OF ATTACHMENT,
  
 FOAM, SCREWS OR NAIL TYPE.SEE
 LIMITATIONS PSF
 2) MISSING THE FL COVERSHEET
 3) MISSING REPORTS FOR UNDERLAYMENT
 D) NOTHING ON SLIDING GLASS DOORS,
 IT DEPENDS ON WHICH BINDER YOU LOOK
  
 IN, STILL NO FL COVER SHEET.
 E) WINDOWS MISSING COVERSHEET FOR ALL
 MODELS.
 F) STRURTURAL COMPONENTS- MISSING ALL
 INFORMATION FL COVER SHEET & REPORT.
 G) RAILINGS MISSING ALL INFO, NO FL
 COVERSHEET OR PRODUCT TESTING REPORT
 H) SOFFIT- NO INFORMATION-
  
 10) COMMENT13 FROM THE PREVIOUS
 REVIEW
 RESPONCE THAT A NEW GEOTECHNICAL REPORT
 WAS TO BE SUBMITTED? NO
 10B) DEALS WITH THE STUCCO STOPPING
 SHORT OF THE SOIL BY 4". THE GYPSUM
 BOARD (2506) STOPS SHORT 8" BUT UNLESS
 THE STUCCO IS DIRECTLY APPLIED TO
 MASONARY AND NOT OVER 5/8" THICK A 4"
 TERMITE INSPECTION AREA IS TO BE LEFT
 WITH NO STUCCO, SEE 1403.1.6.FOR
 VENEERS
 10C) PLANS ALSO ARE TO INDICATE THAT THE
 FOUNDATION IS A MINIMUM OF 12" BELOW
 GRADE, SEE 1804.1.3. SEEE GEOTECH REPORT
 FOR MINIMUM HEIGHT OF FOUNDATION.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026