Plan Review Notes
Plan Review Notes For Permit 04090383
Permit Number 04090383
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-10-28 00:00:001) IN THE BUILDING CLASSIFICATION BOX
 IT INDICATES UNSPRINKLERED THAN IS
 INDICATES SPRINKLER PROTECTION.
  
 2) FIRE ALARM SYSTEMS SHALL BE CLASS A
 OR FULLY ADDRESSABLE NOT CLASS B AS
 NOTED ON SHEET AS-1.
  
 3) REQUIRED FIRE ALARM SYSTEM SHALL
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 4) FIRE SPRINKLER CALCULATIONS DISPLAY
 LESS THAN 5 LBS. SAFETY MARGINS. THIS
 IS NOT ACCEPTABLE.
  
 5) WORK IS TO COMPLY WITH NFPA 241.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR SECURITY GATES.
  
 7) NO FIRE SPRINKLER PLANS PROVIDED
 IN TYPE I PLANS.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR BALCONY RAILINGS.
  
 9) ILLUMINATED EXIT SIGNS ARE REQUIRED
 AT FIRST FLOOR.
  
 10) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE FIRE LINE BACKFLOW DEVICES.
  
 11) PLEASE PROVIDE AN OVERALL SITE
 PLAN DISPLAYING ALL BUILDINGS AND
 ALL FIRE HYDRANTS.
  
 12) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 13) SPEED HUMPS NOTED. THESE DEVICES
 SLOW DOWN FIRE AND PARAMEDICAL
 EQUIPMENT. A 20 FOOT OPENING IS
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910