| 2004-10-28 00:00:00 | 1) IN THE BUILDING CLASSIFICATION BOX |
| | IT INDICATES UNSPRINKLERED THAN IS |
| | INDICATES SPRINKLER PROTECTION. |
| | |
| | 2) FIRE ALARM SYSTEMS SHALL BE CLASS A |
| | OR FULLY ADDRESSABLE NOT CLASS B AS |
| | NOTED ON SHEET AS-1. |
| | |
| | 3) REQUIRED FIRE ALARM SYSTEM SHALL |
| | BE UL LISTED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 4) FIRE SPRINKLER CALCULATIONS DISPLAY |
| | LESS THAN 5 LBS. SAFETY MARGINS. THIS |
| | IS NOT ACCEPTABLE. |
| | |
| | 5) WORK IS TO COMPLY WITH NFPA 241. |
| | |
| | 6) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR SECURITY GATES. |
| | |
| | 7) NO FIRE SPRINKLER PLANS PROVIDED |
| | IN TYPE I PLANS. |
| | |
| | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR BALCONY RAILINGS. |
| | |
| | 9) ILLUMINATED EXIT SIGNS ARE REQUIRED |
| | AT FIRST FLOOR. |
| | |
| | 10) ELECTRONIC SWITCHES ARE REQUIRED |
| | ON THE FIRE LINE BACKFLOW DEVICES. |
| | |
| | 11) PLEASE PROVIDE AN OVERALL SITE |
| | PLAN DISPLAYING ALL BUILDINGS AND |
| | ALL FIRE HYDRANTS. |
| | |
| | 12) WET FIRE HYDRANTS ARE REQUIRED |
| | PRIOR TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 13) SPEED HUMPS NOTED. THESE DEVICES |
| | SLOW DOWN FIRE AND PARAMEDICAL |
| | EQUIPMENT. A 20 FOOT OPENING IS |
| | REQUIRED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |