| Date |
Text |
| 2004-10-07 00:00:00 | *************** UNSAT ****************** |
| | |
| | BLDG TYPE I, BLDG'S 22,23 |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE A |
| | 2001 NEC. PLEASE ALSO SEE GROUNDING |
| | DETAIL/NOTES ON ED-1 REFERENCES CODE |
| | FROM 96 NEC. |
| | WE ARE CURRENTLY UNDER THE 2002 NEC. |
| | |
| | 2)NOTE: PLEASE SEE RISER ON SITE PLAN. |
| | SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| | FROM METER TO MAIN. PLEASE SEE 250.6, |
| | 250.24, AN EQUIP GRND IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 3)NOTE: PLEASE SEE MANY UNITS ARE MISS- |
| | -ING CIRCUITING FOR RECEPT IN LIV RM |
| | AND RECEPT ABOVE DOOR IN CLOSET. |
| | LIV RM ALCOVE AREA. |
| | |
| | 4)NOTE:PLEASE SEE THAT THE "LOCK-OFF" |
| | DEVICE AS NOTED ON PLANS MUST BE |
| | APPROVED BY THE CITY OF WEST PALM BEACH |
| | ELECTRICAL INSPECTION/PLAN REVIEW BEFORE |
| | INSTALLATION AS A MEANS OF LOCK-OFF/ |
| | DISCONNECTING MEANS. |
| | PLEASE SEE THAT A DISCONNECTING MEANS |
| | MAY NOT BE REQUIRED IF PANEL IS W/IN |
| | SITE. |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | NFPA-72 8-1.4.6.1.2 |
| | PLEASE SEE THERE ARE SD'S WHICH NEED TO |
| | BE RELOCATED TO IMMEDIATE VICINITY OF |
| | STAIRS LEADING TO FLOOR ABOVE AND ALSO |
| | AT TOP OF THESE SAME STAIRS. |
| | PLEASE SEE CIRCUITING OF SMOKE DETECTORS |
| | , MANY ARE SHOWN ON SEPARATE CIRCUITS |
| | WITHIN THE SAME UNITS.PLEASE SEE THAT |
| | SD'S ARE REQUIRED TO WIRED IN-LINE, THIS |
| | WOULD NOT BE POSSIBLE AS SHOWN. SOME |
| | ARE SHOWN ON TWO SEPARATE CIRCUITS, SOME |
| | THREE. |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU'S . PLEASE SEE 5.8,8.8 AND 9.0 |
| | KW UNITS. |
| | |
| | 7)NOTE: PLEASE SEE 210.52G FOR MISSING |
| | RECEPT IN GARAGES. PLEASE ALSO SEE 210.8 |
| | FOR RQUIRED GFI PROTECTION. |
| | |
| | 8)NOTE: PLEASE CLARIFY ACCESS TO ATTIC |
| | SPACE ABOVE LOFT UNITS? IT APPEARS THAT |
| | ACCESS IS FROM EACH INDIVIDUAL LOFT UNIT |
| | ? IF THESE ARE AT EACH UNIT FOR EACH |
| | UNIT, THEN THESE LTS WILL BE REQUIRED |
| | TO BE FED FROM THISE UNIT PANESL. |
| | SHOWN ON HOUSE PANEL AT THIS TIME, CIR- |
| | -CUITS #9,11. PLEASE SEE 210.25. |
| | |
| | 9)NOTE: PLEASE NOTE/SPECIFY EACH BRKR |
| | FOR UNITS ON RISER DIAGRAM SHEET. THIS |
| | MAY BE DONE IN A "NOTE" FORM. |
| | |
| | 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS |
| | FOR ALUMINUM CONDUCTORS. PLEASE SEE NOTE |
| | #20A ON ED-1, MENTIONS MIN ALUM #1 FOR |
| | 100A, YET PLANS INDICATE OTHER SIZES. |
| | |
| | 11)NOTE: PLEASE SEE NOTE #24, MENTIONS |
| | DRYER/RANGE RECEPT AS 120/208V, YET |
| | PANELS INDICATE AS VOLTAGE AS 120/240V? |
| | |
| | PLEASE SEE MOST OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON ONE OF THE TYPE I SET |
| | OF PLANS. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIE AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |