Plan Review Notes
Plan Review Notes For Permit 04090383
Permit Number 04090383
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-07 00:00:00*************** UNSAT ******************
  
 BLDG TYPE I, BLDG'S 22,23
  
 1)NOTE: PLEASE SEE PLANS REFERENCE A
 2001 NEC. PLEASE ALSO SEE GROUNDING
 DETAIL/NOTES ON ED-1 REFERENCES CODE
 FROM 96 NEC.
 WE ARE CURRENTLY UNDER THE 2002 NEC.
  
 2)NOTE: PLEASE SEE RISER ON SITE PLAN.
 SHOWS AN EQUIPMENT GROUNDING CONDUCTOR
 FROM METER TO MAIN. PLEASE SEE 250.6,
 250.24, AN EQUIP GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE MANY UNITS ARE MISS-
 -ING CIRCUITING FOR RECEPT IN LIV RM
 AND RECEPT ABOVE DOOR IN CLOSET.
 LIV RM ALCOVE AREA.
  
 4)NOTE:PLEASE SEE THAT THE "LOCK-OFF"
 DEVICE AS NOTED ON PLANS MUST BE
 APPROVED BY THE CITY OF WEST PALM BEACH
 ELECTRICAL INSPECTION/PLAN REVIEW BEFORE
 INSTALLATION AS A MEANS OF LOCK-OFF/
 DISCONNECTING MEANS.
 PLEASE SEE THAT A DISCONNECTING MEANS
 MAY NOT BE REQUIRED IF PANEL IS W/IN
 SITE.
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.6.1.2
 PLEASE SEE THERE ARE SD'S WHICH NEED TO
 BE RELOCATED TO IMMEDIATE VICINITY OF
 STAIRS LEADING TO FLOOR ABOVE AND ALSO
 AT TOP OF THESE SAME STAIRS.
 PLEASE SEE CIRCUITING OF SMOKE DETECTORS
 , MANY ARE SHOWN ON SEPARATE CIRCUITS
 WITHIN THE SAME UNITS.PLEASE SEE THAT
 SD'S ARE REQUIRED TO WIRED IN-LINE, THIS
 WOULD NOT BE POSSIBLE AS SHOWN. SOME
 ARE SHOWN ON TWO SEPARATE CIRCUITS, SOME
 THREE.
  
 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S . PLEASE SEE 5.8,8.8 AND 9.0
 KW UNITS.
  
 7)NOTE: PLEASE SEE 210.52G FOR MISSING
 RECEPT IN GARAGES. PLEASE ALSO SEE 210.8
 FOR RQUIRED GFI PROTECTION.
  
 8)NOTE: PLEASE CLARIFY ACCESS TO ATTIC
 SPACE ABOVE LOFT UNITS? IT APPEARS THAT
 ACCESS IS FROM EACH INDIVIDUAL LOFT UNIT
 ? IF THESE ARE AT EACH UNIT FOR EACH
 UNIT, THEN THESE LTS WILL BE REQUIRED
 TO BE FED FROM THISE UNIT PANESL.
 SHOWN ON HOUSE PANEL AT THIS TIME, CIR-
 -CUITS #9,11. PLEASE SEE 210.25.
  
 9)NOTE: PLEASE NOTE/SPECIFY EACH BRKR
 FOR UNITS ON RISER DIAGRAM SHEET. THIS
 MAY BE DONE IN A "NOTE" FORM.
  
 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS
 FOR ALUMINUM CONDUCTORS. PLEASE SEE NOTE
 #20A ON ED-1, MENTIONS MIN ALUM #1 FOR
 100A, YET PLANS INDICATE OTHER SIZES.
  
 11)NOTE: PLEASE SEE NOTE #24, MENTIONS
 DRYER/RANGE RECEPT AS 120/208V, YET
 PANELS INDICATE AS VOLTAGE AS 120/240V?
  
 PLEASE SEE MOST OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE OF THE TYPE I SET
 OF PLANS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIE AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]