Plan Review Notes
Plan Review Notes For Permit 04090382
Permit Number 04090382
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-01-25 00:00:001. FIRE SPRINKLER CALCUALTIONS IN
 SUBMITTAL PACKAGE STILL DISPLAYS
 A SAFETY MARGIN OF LESS THAN 5LBS.
 PREVIOUS REVIEW COMMENTS INDICATED
 THAT THIS IS NOT ACCEPTABLE. PLEASE
 REVISE.
  
 2. NO EXIT SIGNS SHOWN ON FIRST FLOOR.
  
 THESE NOTES ALSO APPLY TO
  
 04090388
 04090392
 04090393
  
 TYPE IV BUILDINGS
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910