Plan Review Notes
Plan Review Notes For Permit 04090380
Permit Number 04090380
Review Stop B
Sequence Number 5
Notes
Date Text
2005-03-11 00:00:00 
 PERMIT 04090380, 04090382, 04090388,
 04090392 & 04090393
  
 BLDG # 20, 21, 26, 30& 31
  
 4680, 4655, 4630, 4620 & 4610 PORTOFINO
 WAY
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  