Plan Review Notes
Plan Review Notes For Permit 04090380
Permit Number 04090380
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98(AMEND) DESIGN MANUAL
  
 1) SHT A-U14 DETAILS FOR BACKING FOR THE
 TUB, SHOWER, AND W/C SHALL REFLECT THE
 BACKING REQUIREMENTS IN FHA DESIGN MAN-
 UAL PAGES 6.4/6.5, 6.8/6.9/, & 6.12/6.13
  
 2) SHTS P-T41 & P-T41A BUILDING DRAIN DO
 NOT REFLECT THE RISER DIAGRAM ON SHT P-
 T4.3. CLEANOUTS ON DRAIN SHALL BE TWO
 WAY CLEANOUTS IN BLDG DRAIN NOT ON BRAN-
 CH LINES. SHT P-T41 SHOWS RISER P/2B
 THAT IS NOT SHOWN ON RISER. RISER DIAG-
 RAM SHOWS P/2B TAKEN OFF ON THE STACK.
 - SHT P-T14A SHOW RISER 2 & 2A WHERE THE
 RISER DIAGRAM SHOWS 2A & 2B. CLEANOUT
 SHALL BE IN BLDG. DRAIN NOT BRANCH LINE.
 SECTION 104.2.1 PLEASE CORRELATE RISER
 DIAGRAM WITH BLDG DRAIN LAYOUT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]