| Plan Review Notes For Permit 04090380 |
| Permit Number |
04090380 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FHA-98(AMEND) DESIGN MANUAL | | | | | | 1) SHT A-U14 DETAILS FOR BACKING FOR THE | | | TUB, SHOWER, AND W/C SHALL REFLECT THE | | | BACKING REQUIREMENTS IN FHA DESIGN MAN- | | | UAL PAGES 6.4/6.5, 6.8/6.9/, & 6.12/6.13 | | | | | | 2) SHTS P-T41 & P-T41A BUILDING DRAIN DO | | | NOT REFLECT THE RISER DIAGRAM ON SHT P- | | | T4.3. CLEANOUTS ON DRAIN SHALL BE TWO | | | WAY CLEANOUTS IN BLDG DRAIN NOT ON BRAN- | | | CH LINES. SHT P-T41 SHOWS RISER P/2B | | | THAT IS NOT SHOWN ON RISER. RISER DIAG- | | | RAM SHOWS P/2B TAKEN OFF ON THE STACK. | | | - SHT P-T14A SHOW RISER 2 & 2A WHERE THE | | | RISER DIAGRAM SHOWS 2A & 2B. CLEANOUT | | | SHALL BE IN BLDG. DRAIN NOT BRANCH LINE. | | | SECTION 104.2.1 PLEASE CORRELATE RISER | | | DIAGRAM WITH BLDG DRAIN LAYOUT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|