| 2004-10-08 00:00:00 | ********** UNSAT **************** |
| | |
| | BLDG TYPE IV, BLDG #'S,20,21,26,30,31 |
| | |
| | 1)NOTE: PLEASE SEE PLANS TO REFERENCE |
| | 2002 NEC INCLUDING ANY CODES REFERENCED |
| | ON PLANS. |
| | PLEASE SEE GROUNDING DETAIL ON ED-1. |
| | |
| | 2)NOTE: PLEASE SEE SITE RISER DIAGRAM, |
| | EQUIPMENT GRND FROM METER TO MAIN. |
| | 250.6,250.24, THIS SHALL NOT BE INSTALL- |
| | -ED. |
| | |
| | 3)NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | IN UNITS. LIV RM RECEPT/ALCOVE AND |
| | CLOSET RECEPT ABOVE DOOR. |
| | |
| | 4)NOTE: LOCK-OFF DEVICE TO BE APPROVED |
| | BY THIS OFFICE. AHJ. |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | NFPA-72 8-1.4.6.1.2 |
| | PLEASE SEE MULTIPLE CIRCUITS FOR SD'S |
| | IN SOME UNITS. SD'S ARE TO BE WIRED |
| | IN-LINE. MULTIPLE CIRCUITS WOULD NOT |
| | BE POSSIBLE. |
| | |
| | 6)NOTE: PLEASE SEE MIN OCP FOR AHU'S TO |
| | BE 125% PER 424.3B ONLY SOME OF THESE |
| | ARE NOT CORRECT. |
| | |
| | 7)NOTE: PLEASE SEE 210.52G FOR RECEPT |
| | REQUIRED IN GARAGE. MUST ALSO BE GFI, |
| | 210.8 |
| | |
| | 8)NOTE: PLEASE SEE 210.25 FOR ATTIC |
| | LTS FED FROM HOUSE PANEL CIRCUITS 9&11. |
| | IF THESE ARE AT EACH UNIT, THEN THAT |
| | INDIVIDUAL UNIT SHALL FEED EACH LT. |
| | |
| | 9)NOTE: PLEASE NOTE OCP.BRKRS ON RISER/ |
| | METER/MAIN. |
| | |
| | 10)NOTE: PLEASE CORRELATE NOTES FROM |
| | ED-1 WITH PLANS/PANELS/FEEDERS WITH |
| | RESPECT TO ALUM AWG. |
| | |
| | 11)NOTE: PLEASE SEE NOTE# 24 FOR |
| | VOLTAGE VERIFICATION. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |