| Plan Review Notes For Permit 04090369 |
| Permit Number |
04090369 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-03-10 00:00:00 | PERMIT #'S 04090369, 04090385, 04090390, | | | 04090394 & 04090400 | | | | | | BLDGS # 19, 24,28,32 & 34 | | | | | | 4670, 4690, 4695,4710 & 4740 PORTOFINO | | | WAY | | | | | | BUILDING PROVISO: | | | | | | 1)TRUSS DRAWINGS TO BE REVIEWED BY THE | | | DESIGN PROFESSIONAL. | | | | | | 2)TRUSS DRAWINGS TO BE RESUBMITTED | | | BEFORE THE TRUSS ANCHOR AND TRUSS | | | FRAMING INSPECTION WITH CORRECTIONS. | | | .TRUSS ENGINEERING - IF THEY USE | | | "FBC2001/ANSI95" FOR THE CODE, ALONG | | | WITH THE PLATES INCREASE OF 1.33, IT | | | USES A STRESS INCREASE FOR STEEL WHICH | | | IS NOT PERMISSIBLE.THIS IS PER MITEK, | | | THE SOFTWARE COMPANY.THE CORRECT CODE | | | REFERENCE IS "FBC2001/TPI2002", WHICH | | | DOES NOT TAKE A STRESS INCREASE FOR | | | STEEL EVEN IF A 1.33 PLATE INCREASE IS | | | USED. | | | | | | 3) TRUSS SHOP DRAWING TO BE ORIGINAL | | | SIGNATURES AND SEAL OR HAVE A SIGNED & | | | SEALED INDEX PAGE LISTING ALL DRAWINGS. | | | SEE 61G15-23.002(2) | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|