Plan Review Notes
Plan Review Notes For Permit 04090369
Permit Number 04090369
Review Stop E
Sequence Number 2
Notes
Date Text
2004-12-30 00:00:00********* UNSAT 2ND REVIEW *********
  
 BLDG TYPE III
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1: NO. PLEASE SEE PLANS
 STILL REFERENCE THE 2001 NEC. THIS WAS
 CORRECTED ON ED-1, PLEASE SEE AS-1
 PLEASE ALSO SEE ED-1, CODE REFERENCED ON
 PREVIOUS PLANS FROM THE 96 NEC WAS
 CHANGED, HOWEVER CODE IN THE 2002 WHICH
 CORRELATES WITH SAME CODE REFERENCED ON
 PREVIOUS PLANS(96) IS 250.50 FOR
 GROUNDING ELECTRODE SYSTEMS.
  
 2)NOTE: NOTE #2, YES? PLEASE SEE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO MAIN WAS REMOVED AS REQUIRED UNDER
 250.6,250.24, HOWEVER THE EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 10HP PUMP WAS ALSO REMOVED. PLEASE SEE
 250.122 FOR SIZING.
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS
 NOTES, MANY OF THE UNITS ARE STILL
 SHOWING SD'S ON MORE THAN ONE CIRCUIT.
 THESE ARE REQUIRED TO WIRED "IN-LINE",
 IF WIRED AS SHOWN, THEN THERE WOULD BE
 220VON 120V SD'S. PLEASE SEE PLANS, MANY
 OF THESE HAVE BEEN REDLINED ON ONE SET.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE THERE ARE
 UNITS WHICH DO NOT MEET 424.3B
 THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS.
 PLEASE SEE THERE WERE MORE THAN JUST THE
 8KW UNITS.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK
  
 9)NOTE: NOTE #9 YES, THIS WAS DONE,
 HOWEVER, PLEASE SEE BOTH METER CENTERS
 ARE LABLED AS MC#1. (MISPRINT).
  
 10)NOTE: NOTE #10 OK
  
 11)NOTE: NOTE #11 OK
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW