| 2004-12-30 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | BLDG TYPE III |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1: NO. PLEASE SEE PLANS |
| | STILL REFERENCE THE 2001 NEC. THIS WAS |
| | CORRECTED ON ED-1, PLEASE SEE AS-1 |
| | PLEASE ALSO SEE ED-1, CODE REFERENCED ON |
| | PREVIOUS PLANS FROM THE 96 NEC WAS |
| | CHANGED, HOWEVER CODE IN THE 2002 WHICH |
| | CORRELATES WITH SAME CODE REFERENCED ON |
| | PREVIOUS PLANS(96) IS 250.50 FOR |
| | GROUNDING ELECTRODE SYSTEMS. |
| | |
| | 2)NOTE: NOTE #2, YES? PLEASE SEE THE |
| | EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| | TO MAIN WAS REMOVED AS REQUIRED UNDER |
| | 250.6,250.24, HOWEVER THE EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN DISC TO |
| | 10HP PUMP WAS ALSO REMOVED. PLEASE SEE |
| | 250.122 FOR SIZING. |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | 4)NOTE: NOTE #4 OK |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS |
| | NOTES, MANY OF THE UNITS ARE STILL |
| | SHOWING SD'S ON MORE THAN ONE CIRCUIT. |
| | THESE ARE REQUIRED TO WIRED "IN-LINE", |
| | IF WIRED AS SHOWN, THEN THERE WOULD BE |
| | 220VON 120V SD'S. PLEASE SEE PLANS, MANY |
| | OF THESE HAVE BEEN REDLINED ON ONE SET. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE THERE ARE |
| | UNITS WHICH DO NOT MEET 424.3B |
| | THE AMPACITY OF THE BRANCH-CIRCUIT |
| | CONDUCTORS AND THE RATING OR SETTING OF |
| | OVERCURRENT PROTECTIVE DEVICES SUPPLYING |
| | FIXED ELECTRIC SPACE-HEATING EQUIPMENT |
| | CONSISTING OF RESISTANCE ELEMENTS WITH |
| | OR WITHOUT A MOTOR SHALL NOT BE LESS |
| | THAN 125 PERCENT OF THE TOTAL LOAD OF |
| | THE MOTORS AND THE HEATERS. |
| | PLEASE SEE THERE WERE MORE THAN JUST THE |
| | 8KW UNITS. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 OK |
| | |
| | 9)NOTE: NOTE #9 YES, THIS WAS DONE, |
| | HOWEVER, PLEASE SEE BOTH METER CENTERS |
| | ARE LABLED AS MC#1. (MISPRINT). |
| | |
| | 10)NOTE: NOTE #10 OK |
| | |
| | 11)NOTE: NOTE #11 OK |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND INSERT NEW SHEETS INTO THREE |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |