| Plan Review Notes For Permit 04090369 |
| Permit Number |
04090369 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-22 00:00:00 | DENIED:TYPE III BUILDING #19 | | | 1.PER 2001 FBC(M) 601.4 EXCEPTION #2 | | | & 3, RETURN TRANSFER GRILLES SHALL BE | | | SIZED AS FOLLOWS: | | | RETURN TRANSFER - 50 SQ INCHES OF FREE | | | AREA TO 100 CFM OF SUPPLY AIR TO THAT | | | AREA.ALL SUPPLY AIR INTO THE MASTER | | | SUITE SHALL BE INCLUDED FOR PROPER | | | SIZING. | | | THE FOLLOWING UNITS ARE NOT SIZED | | | PROPERLY - A-1 (DWG AC-U1), A-1S (DWG | | | AC-U2), A-1LS (AC-U4), B-2 (AC-U5), C-3 | | | (AC-U9), C-3S (AC-U10). | | | | | | 2.PLEASE NOTE, THE TOILET EXHAUST | | | TERMINATION SHALL BE SCREENED PER 2001 | | | FBC(M) 401.6. (DRYER EXHAUST SHALL BE | | | NON-SCREENED). | | | | | | 3.PLAN SHEET PD-1 CONDENSATE RISER, | | | CONDENSATE SHALL TERMINATE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|