| Plan Review Notes For Permit 04090369 |
| Permit Number |
04090369 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-07 00:00:00 | 1) WORK IS TO COMPLY WITH NFPA 241. | | | | | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 3) ILLUMINATED EXIT SIGNS ARE REQUIRED | | | ON THE FIRST FLOOR. | | | | | | 4) FIRE ALARM SYSTEMS SHALL BE CLASS A | | | OR FULLY ADDRESSABLE. | | | | | | 5) FIRE ALARM SYSTEMS SHALL BE UL LISTED | | | FOR CENTRAL STATION SERVICE. | | | | | | 6) ELECTRONIC SWITHES ARE REQUIRED ON | | | THE FIRE LINE BACKFLOW DEVICES. | | | | | | 7) PLEASE PROVIDE PERSCRIPTIVE STRENGTH | | | REQUIREMENTS FOR BALCONY RAILINGS. | | | | | | 8) THE SAFETY MARGIN FOR FIRE SPRINKLER | | | CALCULATION IS LESS THAN 5 LBS FOR BLDG | | | TYPE III AND TYPE IV. THIS IS NOT | | | ACCEPTABLE. | | | | | | REVIEW NOTES ARE FOR PERMITS 04090385, | | | 04090390, 04090394, 04090400 | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|