| 2004-10-08 00:00:00 | ************* UNSAT *************** |
| | |
| | BLDG TYPE III,BLDG'S 19,24,28,32,34 |
| | |
| | 1)NOTE: PLEASE SEE PLANS FOR REFERENCE |
| | OF CODE. SHOULD BE 2002 NEC. |
| | PLEASE ALSO SEE ED-1 FOR CODE REFERENCED |
| | FROM 96 NEC. |
| | |
| | 2)NOTE: PLEASE SEE EQUIPMNET GROUNDING |
| | CONDUCTOR ON SITE RISER FROM METER TO |
| | MAIN. THIS IS NOT PERMITTED. 250.6,250. |
| | .24. |
| | |
| | 3)NOTE: PLEASE SEE CIRCUITING FOR ALL |
| | UNITS, SOME UNIT MISSING. LIV RM RECEPT |
| | AND CLOSET RECEPT. |
| | |
| | 4)NOTE: PLEASE SEE "LOCK-OFF" DEVICE TO |
| | BE APPROVED BY CITY OF WEST PALM BEACH |
| | BEFORE USE. |
| | IF PANEL IS W/IN SITE, THIS DEVICE MAY |
| | NOT BE REQUIRED? |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | NFPA-72 8-1.4.6.1.2 |
| | PLEASE SEE SD'S ON MULTIPLE CIRCUITS |
| | IN MANY OF THE UNTIS. THESE ARE REQUIRED |
| | TO BE WIRED "IN-LINE". THIS WOULD NOT BE |
| | POSSIBLE AS SHOWN. |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR OCP OF |
| | AHU'S. SOME OK, SOME NEED TO BE ADJUSTED |
| | FOR MIN REQUIREMENTS. 125%. |
| | |
| | 7)NOTE: PLEASE SEE 210.52G FOR MISSING |
| | RECEPT IN GARAGE'S. PLEASE ALSO SEE |
| | 210.8 FOR GFI REQUIREMENT. |
| | |
| | 8)NOTE: PLEASE SEE LTS IN ATTICS IN LOFT |
| | UNITS MUST BE SERVED FROM EACH OF THOSE |
| | UNITS PANELS. 210.25 |
| | |
| | 9)NOTE: PLEASE NOTE OR SPECIFY OCP/BRKRS |
| | FOR APT PANELS AT METER/MAIN LOCATION |
| | ON RISER. THIS MAY BE IN A "TYPICAL" |
| | NOTE FORM. |
| | |
| | 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS |
| | AND NOTE # 20A ON ED-1. |
| | |
| | 11)NOTE: PLEASE SEE NOTE #24, SHOWS 120/ |
| | 208V YET PANELS INDICATE 120/240V. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |