Plan Review Notes
Plan Review Notes For Permit 04090369
Permit Number 04090369
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-08 00:00:00************* UNSAT ***************
  
 BLDG TYPE III,BLDG'S 19,24,28,32,34
  
 1)NOTE: PLEASE SEE PLANS FOR REFERENCE
 OF CODE. SHOULD BE 2002 NEC.
 PLEASE ALSO SEE ED-1 FOR CODE REFERENCED
 FROM 96 NEC.
  
 2)NOTE: PLEASE SEE EQUIPMNET GROUNDING
 CONDUCTOR ON SITE RISER FROM METER TO
 MAIN. THIS IS NOT PERMITTED. 250.6,250.
 .24.
  
 3)NOTE: PLEASE SEE CIRCUITING FOR ALL
 UNITS, SOME UNIT MISSING. LIV RM RECEPT
 AND CLOSET RECEPT.
  
 4)NOTE: PLEASE SEE "LOCK-OFF" DEVICE TO
 BE APPROVED BY CITY OF WEST PALM BEACH
 BEFORE USE.
 IF PANEL IS W/IN SITE, THIS DEVICE MAY
 NOT BE REQUIRED?
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.6.1.2
 PLEASE SEE SD'S ON MULTIPLE CIRCUITS
 IN MANY OF THE UNTIS. THESE ARE REQUIRED
 TO BE WIRED "IN-LINE". THIS WOULD NOT BE
 POSSIBLE AS SHOWN.
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP OF
 AHU'S. SOME OK, SOME NEED TO BE ADJUSTED
 FOR MIN REQUIREMENTS. 125%.
  
 7)NOTE: PLEASE SEE 210.52G FOR MISSING
 RECEPT IN GARAGE'S. PLEASE ALSO SEE
 210.8 FOR GFI REQUIREMENT.
  
 8)NOTE: PLEASE SEE LTS IN ATTICS IN LOFT
 UNITS MUST BE SERVED FROM EACH OF THOSE
 UNITS PANELS. 210.25
  
 9)NOTE: PLEASE NOTE OR SPECIFY OCP/BRKRS
 FOR APT PANELS AT METER/MAIN LOCATION
 ON RISER. THIS MAY BE IN A "TYPICAL"
 NOTE FORM.
  
 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS
 AND NOTE # 20A ON ED-1.
  
 11)NOTE: PLEASE SEE NOTE #24, SHOWS 120/
 208V YET PANELS INDICATE 120/240V.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]