2004-10-27 00:00:00BUILDING PLAN REVIEW
  
 PORTOFINO PHASE II LAND, LTC
 BUILDING TYPE III
  
 PERMIT:04090369BLDG# 19
 ADD: 4670 PORTOFINO WAY
 PERMIT:04090385BLDG# 24
 ADD: 4690 PORTOFINO WAY
 PERMIT:04090390BLDG# 28
 ADD: 4695 PORTOFINO WAY
 PERMIT:04090394BLDG# 32
 ADD: 4710 PORTOFINO WAY
 PERMIT:04090400BLDG#34
 ADD: 4740 PORTOFINO WAY
 CONT: EPOCH PROPERTIES, INC
 TEL: (407)718-8932
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE INCORRECT PROPERTY CONTROL NUMBER
 WAAS USED ON THE PERMIT APPLICATION ALSO
 CORRECT THE ADDRESSES FOR PHASE II, USE
 THE LIST DATED SEPT 21/04.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) SHEET A-U13 DETAILS INDICATE THE USE
 OF SEMCO STRAPS. SEMCO WAS BOUGHT OUT IN
 1999 BY USP, UPDATE PLANS TO REFLECT THE
 MANUFACTURER, MODEL NUMBER AND LOADS TO
 BE IMPOSED.SHEET A-T1.3 HURRICANE STRAP/
 CONNECTIONNOTES ALSO REFRENCE PRODUCTS
 DELETE SEMCO FROM A-DT4.
  
 4) SHEET A-U13 DETAIL# 5, RISERS ARE TO
 COMPLY WITH 1007.3.1. RISERS SHALL BE A
 MAXIMUM OF 7".
  
 5) SHEET A-T3.3 ROOF SHEATHING NOTES, 23
 .22.2.5 DEALS WITH THE HIGH VELOCITY
 HURRICANE ZONES, 22306.1* ZONE 3 EDGE
 NAILING ZONES BETWEEN 25'-35' REQUIRE
 8D RING SHANK NAILS @ 4"O.C. EDGES &
 6"O.C. FOR INTERMEDIATES.
 ENGINEER OF RECORD WILL PROVIDE ADDITION
 AL INFORMATION ON ROOF SHEATHING NAILING
 ABOVE 35'.
  
 6) SHEET A-T3.3 HURRICANE STRAPS:
 A) USP TSU24/26 TUNNEL TIE NOT LISTED
 IN THE 2004 CATALOG.
 B) USP DTC LISTED IN THE USP CATALOG AS
 A ROOF TRUSS CLIP, UPDATE LISTING.
 C) USP RT24 VALUE ON THE PLANS IS HIGH,
 SEE FOOTNOTE IN USP (VALUE REPRESENT
 LOADS WHICH DO NOT INCLUDE A STEEL
 INCREASE ON THE STEEL CALCULATION.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 7)903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
  
 8) A-DT1 WINDOW & DOOR SCHEDULE, PLANS
 DO NOT INDICATE IF THIS SCHEDULE IS FOR
 THE INTERIOR ZONE (4) OR END ZONE(5).
 ALSO THERE IS A MULTIPLIER OF 1.12 FOR
 OVER 40' SEE 1606.2D.
  
 9) ADT1 HARDWARE NOTES (6) IMPLIES THAT
 ON THE 2ND & 3RD FLOORS ONLY THE SLIDING
 GLASS DOORS REQUIRES IMPACT DOORS. THE C
 ITY'S OFFICIAL INTERPRETATION LIST ON
 LARGE PROJECTS THAT A PRESTORM PREPARED-
 NESS PLAN MUST BE SUBMITTED BY THE PROP-
 ERTY OWNERS OR MANAGING AGENT FOR REVIEW
 BY THE CONSTRUCTION DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINIMUM ON-SITE
 LOCATION OF SHUTTERS, PARTY RESPONSIBLE
 FOR SECURRING SHUTTERS, (SAID PARTY
 RESPONSIBLE FOR SECURRING THE SHUTTERS,
 SAID PARTY MUST LIVE WITHIN PALM BEACH
 COUNTY) THE TOTAL NUMBER OF OPENINGS TO
 BE PROTECTED & THE TOTAL TIME REQUIRED
 TO SECURE ALL OPENINGS. PROTECTION OF
 OPENINGS SHALL BE ACCOMPLISHED WITHIN
 (12) HRS OR LESS OF THE NATIONAL WEATHER
 SERVICE OFA HURRICANE WATCH.
  
 10) SHEET A-DT2 DETAILS 7&8 PROVIDE A
 CLEAR DETAIL OF THE STUCCO REVEL & THE
 EXSPANSION CONTROL JOINT, (ASTM C-1063)
 INDICATE HOW THE WATER TIGHT MEMBRANE
 WILL OCURR, BE INSTALLED?
  
 11)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 GEOTECH REPORTS ARE NOT SIGNED& SEALED.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRONT DOOR MASONITE REPORTS ARE
 ILLEGABLE, PROVIDE CLEAR COPIES
 B) CLOSPAY GARAGE DOORS MISSING THE
 FLORIDA PRODUCT APPROVAL COVER SHEET.
 C) ROOFING ASSEMBLIES
 1) HANSON ROOF TILE INDICATE THE METHOD
 OF ATTACHMENT
 2) MISSING THE FLORIDA COVER SHEET
 3) MISSING REPORTS FOR THE UNDERLAYMENT
 D) NOTHING ON THE SLIDING GLASS DOOR
 E) WINDOWS- MISSING THE FLORIDA PRODUCT
 APPROVAL COVER SHEET
 F) STRUCTURAL COMPONENTS- MISSING INFOR-
 MATION FOR TRUSS ANCHORS, FL APPROVAL.
 G) RAILINGS NO INFORMATION SUBMITTED
 H) SOFFITS(EXTERIOR) NO INFORMATION
  
 14) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE SEEMS TO BE DESCREPANCIES IN
 THE FOUNDATION AND THE RECOMENDATION OF
 THE GEOTECH ENGINEER. THE STRUCTURAL
 SHEETS INDICATE A WF-6A FOUNDATION. THE
 GEOTECH REPORT RECOMENDS THE FOUNDATION
 TO BE 18" BELOW FINISH GRADE & A MINIMUM
 OF 24" WIDE, WHY WAS THE GEOTECH REPORT
 RECOMMENDATION NOT FOLLOWED?
 THE SECOND ISSUE WITH THE FOUNDATION
 DEALS WITH THE APPLICATION OF GYPSUM
 WALLBOARD SHEATHING, 2504.4.1 DEALS WITH
 THE APPLICATION OF EXTERIOR GYPSUM WALL
 BOARD SHEATHING, THE GYPSUM BASE VENEER
 SHALL BE INSTALLED IN ACORDANCE WITH
 2506 OR GA 216. IN GA 216-4.6.6 GYPSUM
 BOARD USED IN BUILDING CONSTRUCTION SHAL
 L BE NOT LESS THAN 8" FROM FINISH GRADE
 IN FULLY WEATHER AND WEATHER PROTECTED
 SIDING SYSTEMS.
 THE ADDITIONAL 8" FROM THE BOTTOM OF THE
 GYPSUM BOARD TO GRADE HAS NOT BEEN ADD-
 RESSED?
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026