| Plan Review Notes For Permit 04090363 |
| Permit Number |
04090363 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FHA-98(AMEND) DESIGN MANUAL | | | | | | 1) SHT A-U14 DETAILS FOR BACKING FOR | | | THE | | | TUB, SHOWER, AND W/C SHALL REFLECT THE | | | BACKING REQUIREMENTS IN FHA DESIGN MAN- | | | UAL PAGES 6.4/6.5, 6.8/6.9, & 6.12/6.13 | | | 2) SHT P-T2.1 THE BLDG DRAIN LAYOUT | | | DOES | | | NOT REFLECT THE RISER DIAG. UPSTREAM OF | | | THE BLDG CLEANOUT THE 2" PIPING FOR THE | | | WASH MACHINES. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|