Plan Review Notes
Plan Review Notes For Permit 04090363
Permit Number 04090363
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-07 00:00:00************** UNSAT *******************
  
 BLDG TYPE II, BLDG'S 18,25,27,29,33
  
 1)NOTE: PLEASE SEE PLANS REFERENCE A
 2001 NEC. PLEASE ALSO SEE GROUNDING
 DETAIL/NOTES ON ED-1 REFERENCES CODE
 FROM 96 NEC.
 WE ARE CURRENTLY UNDER THE 2002 NEC.
  
 2)NOTE: PLEASE SEE RISER IN SITE PLAN.
 SHOWS AN EQUIPMENT GROUNDING CONDUCTOR
 INSTALLED FROM METER TO MAIN. PLEASE
 SEE 250.6,250.24
  
 3)NOTE: PLEASE SEE MANY UNITS ARE MISS-
 -ING CIRCUITING SHOWN FOR RECEPT ABOVE
 DOOR IN CLOSET AND RECEPT IN LIVING RM
 ALCOVE AREA.
  
 4)NOTE: PLEASE SEE "LOCK-OFF " BRKR
 MUST BE APPROVED BY THE CITY OF WEST
 PALM BEACH BEFORE USE AS MEANS OF DISC
 FOR WATER HEATER. IF WH IS W/IN SITE,
 THERE IS NO NEED FOR THIS.
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.6.1.2
 PLEASE SEE THERE ARE SD'S WHICH ONLY
 NEED TO BE RELOCATED TO AREA OF STAIRS
 LEADING TO FLOOR ABOVE AND AT THE TOP OF
 STAIRS.
 PLEASE ALSO SEE CIRCUITING FOR SD'S IN
 MANY OF THE 2/3 BEDRM UNITS. SOME SHOW
 SD'S BEING ON UP TO THREE SEPARATE
 CIRCUITS IN ONE UNIT. SMOKE DETECTORS
 ARE REQUIRED TO BE WIRED IN-LINE AND IF
 ON THREE SEPARATE CIRCUITS, THIS WOULD
 NOT BE POSSIBLE.
  
 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 REQUIRED FOR AHU'S. PLEASE THIS ONLY
 APPLIES TO SOME OF THE UNITS.
  
 7)NOTE:PLEASE SEE 210.52G FOR RECEPT
 IN GARAGE'S. PLEASE ALSO SEE 210.8 FOR
 GFI PROTECTION.
  
 8)NOTE: PLEASE CLARIFY ACCESS TO ATTIC
 IN LOFT UNITS. IT APPEARS THESE ARE
 ACCESSIBLE FROM EACH UNIT, YET LT IS FED
 FROM HOUSE PANEL. IF THESE ARE AT EACH
 UNIT AND USED FOR THOSE UNITS, THEN THAT
 PARTICULAR ATTIC LT MUST BE FED FROM
 THAT INDIVIDUAL UNIT PANEL.
 210.25
  
 9)NOTE: PLEASE NOTE/SPECIFY OCP/BRKRS
 AT METER CENTERS. CAN BE IN NOTE FORM.
  
 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS
 FOR ALUMIMUN CONDUCTORS WITH NOTE #20A
 ON NOTES SHEET.
 MENTIONS ALL ALUM TO BE NO SMALLER THAN
 #1 FOR 100A'S?
  
 11)NOTE: PLEASE SEE NOTE #24 ON ED-1,
 THIS MENTIONS VOLTAGE AT 120/208V,
 PLEASE SEE PANELS INDICATE 120/240V
  
 PLEASE SEE SOME OF THESE ABOVE ITEMS
 HAVE BEEN REDLINED ON ONE OF THE SETS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]