| 2004-10-07 00:00:00 | ************** UNSAT ******************* |
| | |
| | BLDG TYPE II, BLDG'S 18,25,27,29,33 |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE A |
| | 2001 NEC. PLEASE ALSO SEE GROUNDING |
| | DETAIL/NOTES ON ED-1 REFERENCES CODE |
| | FROM 96 NEC. |
| | WE ARE CURRENTLY UNDER THE 2002 NEC. |
| | |
| | 2)NOTE: PLEASE SEE RISER IN SITE PLAN. |
| | SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| | INSTALLED FROM METER TO MAIN. PLEASE |
| | SEE 250.6,250.24 |
| | |
| | 3)NOTE: PLEASE SEE MANY UNITS ARE MISS- |
| | -ING CIRCUITING SHOWN FOR RECEPT ABOVE |
| | DOOR IN CLOSET AND RECEPT IN LIVING RM |
| | ALCOVE AREA. |
| | |
| | 4)NOTE: PLEASE SEE "LOCK-OFF " BRKR |
| | MUST BE APPROVED BY THE CITY OF WEST |
| | PALM BEACH BEFORE USE AS MEANS OF DISC |
| | FOR WATER HEATER. IF WH IS W/IN SITE, |
| | THERE IS NO NEED FOR THIS. |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | NFPA-72 8-1.4.6.1.2 |
| | PLEASE SEE THERE ARE SD'S WHICH ONLY |
| | NEED TO BE RELOCATED TO AREA OF STAIRS |
| | LEADING TO FLOOR ABOVE AND AT THE TOP OF |
| | STAIRS. |
| | PLEASE ALSO SEE CIRCUITING FOR SD'S IN |
| | MANY OF THE 2/3 BEDRM UNITS. SOME SHOW |
| | SD'S BEING ON UP TO THREE SEPARATE |
| | CIRCUITS IN ONE UNIT. SMOKE DETECTORS |
| | ARE REQUIRED TO BE WIRED IN-LINE AND IF |
| | ON THREE SEPARATE CIRCUITS, THIS WOULD |
| | NOT BE POSSIBLE. |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | REQUIRED FOR AHU'S. PLEASE THIS ONLY |
| | APPLIES TO SOME OF THE UNITS. |
| | |
| | 7)NOTE:PLEASE SEE 210.52G FOR RECEPT |
| | IN GARAGE'S. PLEASE ALSO SEE 210.8 FOR |
| | GFI PROTECTION. |
| | |
| | 8)NOTE: PLEASE CLARIFY ACCESS TO ATTIC |
| | IN LOFT UNITS. IT APPEARS THESE ARE |
| | ACCESSIBLE FROM EACH UNIT, YET LT IS FED |
| | FROM HOUSE PANEL. IF THESE ARE AT EACH |
| | UNIT AND USED FOR THOSE UNITS, THEN THAT |
| | PARTICULAR ATTIC LT MUST BE FED FROM |
| | THAT INDIVIDUAL UNIT PANEL. |
| | 210.25 |
| | |
| | 9)NOTE: PLEASE NOTE/SPECIFY OCP/BRKRS |
| | AT METER CENTERS. CAN BE IN NOTE FORM. |
| | |
| | 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS |
| | FOR ALUMIMUN CONDUCTORS WITH NOTE #20A |
| | ON NOTES SHEET. |
| | MENTIONS ALL ALUM TO BE NO SMALLER THAN |
| | #1 FOR 100A'S? |
| | |
| | 11)NOTE: PLEASE SEE NOTE #24 ON ED-1, |
| | THIS MENTIONS VOLTAGE AT 120/208V, |
| | PLEASE SEE PANELS INDICATE 120/240V |
| | |
| | PLEASE SEE SOME OF THESE ABOVE ITEMS |
| | HAVE BEEN REDLINED ON ONE OF THE SETS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY HAVE AN AFFECT |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |