| Plan Review Notes For Permit 04090292 |
| Permit Number |
04090292 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-11-05 00:00:00 | | | | | | | BUILDING PANS REVIEW FAILED | | | | | | THE SUBMITTALS FOR THE BUTT GLASS | | | ASSEMBLY IS MISSING INFORMATION: | | | | | | 1. #1 ON SITE SPECIFIC FORM NOT SHOWING | | | METHOD BEING USED. (METHOD 1 OR 2) | | | | | | 2. THE ENGINEER'S DRAWING SHOWING THE | | | WINDOW SIZES & DETAILS SHOW 4000T IN | | | DETAIL A/1.THE PRODUCT APPROVAL ARE | | | FOR THE 4500 SERIES. | | | | | | 3.THE OVER ALL SIZE OF THE BUTT GLASS | | | ASSEMBLY SHOWN ON THE PLANS MUST BE THE | | | SAME AS THOSE SHOWN ON THE ARCHITECT'S. | | | SHEET. | | | | | | 4. THE ENGINEER HAS SUBMITTED TWO | | | DIFFERENT DETAIL PLANS. THE DRAWINGS | | | HAVE DIFFERENT INFORMATION: IE DESIGN | | | PRESSURE, GLASS THICKNESS, DRAWINGS ARE | | | DIFFERENT, MAX. SILICONE STRESS, ETC. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 | | | |
|