Plan Review Notes
Plan Review Notes For Permit 04090292
Permit Number 04090292
Review Stop B
Sequence Number 3
Notes
Date Text
2004-11-05 00:00:00 
  
 BUILDING PANS REVIEW FAILED
  
 THE SUBMITTALS FOR THE BUTT GLASS
 ASSEMBLY IS MISSING INFORMATION:
  
 1. #1 ON SITE SPECIFIC FORM NOT SHOWING
 METHOD BEING USED. (METHOD 1 OR 2)
  
 2. THE ENGINEER'S DRAWING SHOWING THE
 WINDOW SIZES & DETAILS SHOW 4000T IN
 DETAIL A/1.THE PRODUCT APPROVAL ARE
 FOR THE 4500 SERIES.
  
 3.THE OVER ALL SIZE OF THE BUTT GLASS
 ASSEMBLY SHOWN ON THE PLANS MUST BE THE
 SAME AS THOSE SHOWN ON THE ARCHITECT'S.
 SHEET.
  
 4. THE ENGINEER HAS SUBMITTED TWO
 DIFFERENT DETAIL PLANS. THE DRAWINGS
 HAVE DIFFERENT INFORMATION: IE DESIGN
 PRESSURE, GLASS THICKNESS, DRAWINGS ARE
 DIFFERENT, MAX. SILICONE STRESS, ETC.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  