2005-05-03 00:00:00***** UNSAT *****
  
 PLEASE SEE PLANS APPEAR TO BE FOR
 FINALS.
 PLEASE MAKE THE CORRECTIONS LISTED
 BELOW.
  
  
 1)NOTE: PLEASE SEE PLANS INDUCATE TWO
 MAIN DISCONNECTS OUTSIDE NEXT TO METER,
 HOWEVER RISER DOES NOT SHOW ANY MAINS.
 PLEASE CORRELATE.
 215.5
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE,
 PLEASE SEE ONE SMALL APPL CIRCUIT IS
 SHOWN WITH 3KW LOAD ON A 1-POLE 20A
 CIRCUIT. (1.5KW)?
 310.16,240.4 ETC
  
 3)NOTE: PLEASE SEE LOAD SHOWN ON POOL
 PANEL IS SHOWN AT 1.55 A'S. PLEASE SEE
 3.73KW @240 IS 15.54A'S (MISPRINT).
  
 4)NOTE: PLEASE SEE DRYER IS SHOWN WITH
 5KW LOAD ON A 1-P20A CIRCUIT. PLANS
 INDICATE DRYER AS GAS?
  
 5)NOTE: PLEASE VERIFY #OF #6 CONDUCTORS
 SHOWN FOR OVEN AND COOK-TOP. IF SHOWN
 WITH 4-#6'S THEN THESE WOULD BE
 REQUIRED.
 PLEASE ALSO SEE #6'S SHOWN FOR 40A OCP
 FOR EACH COND UNIT?
 PLEASE VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  