| Plan Review Notes For Permit 04090292 |
| Permit Number |
04090292 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-03 00:00:00 | ***** UNSAT ***** | | | | | | PLEASE SEE PLANS APPEAR TO BE FOR | | | FINALS. | | | PLEASE MAKE THE CORRECTIONS LISTED | | | BELOW. | | | | | | | | | 1)NOTE: PLEASE SEE PLANS INDUCATE TWO | | | MAIN DISCONNECTS OUTSIDE NEXT TO METER, | | | HOWEVER RISER DOES NOT SHOW ANY MAINS. | | | PLEASE CORRELATE. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE PANEL SCHEDULE, | | | PLEASE SEE ONE SMALL APPL CIRCUIT IS | | | SHOWN WITH 3KW LOAD ON A 1-POLE 20A | | | CIRCUIT. (1.5KW)? | | | 310.16,240.4 ETC | | | | | | 3)NOTE: PLEASE SEE LOAD SHOWN ON POOL | | | PANEL IS SHOWN AT 1.55 A'S. PLEASE SEE | | | 3.73KW @240 IS 15.54A'S (MISPRINT). | | | | | | 4)NOTE: PLEASE SEE DRYER IS SHOWN WITH | | | 5KW LOAD ON A 1-P20A CIRCUIT. PLANS | | | INDICATE DRYER AS GAS? | | | | | | 5)NOTE: PLEASE VERIFY #OF #6 CONDUCTORS | | | SHOWN FOR OVEN AND COOK-TOP. IF SHOWN | | | WITH 4-#6'S THEN THESE WOULD BE | | | REQUIRED. | | | PLEASE ALSO SEE #6'S SHOWN FOR 40A OCP | | | FOR EACH COND UNIT? | | | PLEASE VERIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|