| Plan Review Notes For Permit 04090215 |
| Permit Number |
04090215 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-02 00:00:00 | BUILDING PROVISO: | | | | | | 803.4 FOAM PLASTIC TRIM SHALL NOT BE | | | USED AS INTERIOR TRIM. SEE EXCEPTION: | | | A) THE MINIMUM DENSITY IS 20LBS/CU FT. | | | B) THE MAXIMUM THICKNESS OF THE TRIM IS | | | 1/2" AND THE MAXIMUM WIDTH IS 4".C) | | | THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE WALL OR CEILING. | | | D) THE FLAMESPREAD RATING DOES NOT | | | EXCEED 75 WHEN TESTED PER ASTM E 84. | | | THE SMOKE DEVELOPMENT RATING IS | | | NOT LIMITED. |
|