Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SUBMIT A SANITARY RISER DIAGRAM THAT
 INDICATES ALL ADDED FIXTURES. SHOW PIPE
 SIZE AND VENTING FOR NEW FIXTURES.
 SECTION 104.2.1
 2) SUBMIT A DETAIL SHOWING PIPING FOR
 THE RELIEF VALVE FOR THE STEAM UNIT. IN-
 DICATE TERMINATION POINT FOR RELIEF VAL-
 VE PIPING. SECTION 104.2.1 & 504.7.1.
 3) CLARIFY NOTE "MINOR WORK IN THESE
 AREAS"
  