Plan Review Notes
Plan Review Notes For Permit 04090215
Permit Number 04090215
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-05 00:00:00*********** UNSAT ********
  
 1)NOTE: PLEASE SHOW NEW CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 215.5
  
 2)NOTE: PLEASE CORRELATE OCP AND AWG FOR
 SOME ITEMS ON PANEL SCHEDULES.
 60A OCP W/ #8
 20A OCP W/ #14
 COOKTOP, WATER HEATER, FRIG , EXISTING
 COOKTOP. PLEASE SEE 310.16 75 DEGREE
 COL. 110.14
  
 3)NOTE: PLEASE SUBMIT SPEC SHEETS FOR
 NEW SAUNA/ STEAM UNITS.
 LOADS SHOWN AT 5KW YET OCP IS SHOWN AT
 60A ALSO WITH #8 AWG??
 310.16,215.5
  
 4)NOTE: PLEASE VERIFY NEW DISHWASHER
 SHOWN AT 240V?
  
 5)NOTE: PLEASE CLARIFY SOME AREAS OF
 PLANS CALL FOR MINOR WORK, YET NOTHING
 IS INDICATED?
  
 6)NOTE: PLEASE SEE NOTE #8 OF ELECTRICAL
 NOTES. PLEASE SEE NEC 336 OF THE 2002
 NEC, NMC IS NOT PERMITTED IN THIS BLDG.
 THIS IS ONLY A NOTE FYI.
  
 7)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 IN REFERENCE TO REQUIRED UNITY OF TITLE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  