| 2004-10-05 00:00:00 | *********** UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SHOW NEW CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE CORRELATE OCP AND AWG FOR |
| | SOME ITEMS ON PANEL SCHEDULES. |
| | 60A OCP W/ #8 |
| | 20A OCP W/ #14 |
| | COOKTOP, WATER HEATER, FRIG , EXISTING |
| | COOKTOP. PLEASE SEE 310.16 75 DEGREE |
| | COL. 110.14 |
| | |
| | 3)NOTE: PLEASE SUBMIT SPEC SHEETS FOR |
| | NEW SAUNA/ STEAM UNITS. |
| | LOADS SHOWN AT 5KW YET OCP IS SHOWN AT |
| | 60A ALSO WITH #8 AWG?? |
| | 310.16,215.5 |
| | |
| | 4)NOTE: PLEASE VERIFY NEW DISHWASHER |
| | SHOWN AT 240V? |
| | |
| | 5)NOTE: PLEASE CLARIFY SOME AREAS OF |
| | PLANS CALL FOR MINOR WORK, YET NOTHING |
| | IS INDICATED? |
| | |
| | 6)NOTE: PLEASE SEE NOTE #8 OF ELECTRICAL |
| | NOTES. PLEASE SEE NEC 336 OF THE 2002 |
| | NEC, NMC IS NOT PERMITTED IN THIS BLDG. |
| | THIS IS ONLY A NOTE FYI. |
| | |
| | 7)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | IN REFERENCE TO REQUIRED UNITY OF TITLE. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |