| 2004-10-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04090215 |
| | ADD: 201 S NARCISSUS AV |
| | CONT: HOME TECHNICAL SERVICES, INC |
| | TEL: (561)262-4068 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS INDICATE THE USE OF SOFFITS, NO |
| | DETAILS FOR FASTENING TO THE STRUCTURE |
| | ABOVE, NOR SPACING OF FRAMING OR FASTEN- |
| | ING OF FRAMING. |
| | |
| | 3) 609.2.1 TYPE I OR II BUILDINGS, NO |
| | COMBUSTIBLE MATERIALS IN WALLS, STUDS, |
| | BACKING, ETC. |
| | |
| | 4) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 5)803.4 FOAM PLASTIC TRIM SHALL NOT BE |
| | USED AS INTERIOR TRIM. SEE EXCEPTION: |
| | A) THE MINIMUM DENSITY IS 20LBS/CU FT. |
| | B) THE MAXIMUM THICKNESS OF THE TRIM IS |
| | 1/2" AND THE MAXIMUM WIDTH IS 4". |
| | C) THE TRIM CONSTITUTES NO MORE THAN |
| | 10% OF THE WALL OR CEILING. |
| | D) THE FLAMESPREAD RATING DOES NOT |
| | EXCEED 75 WHEN TESTED PER ASTM E 84. |
| | THE SMOKE DEVELOPMENT RATING IS |
| | NOT LIMITED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |