Plan Review Notes
Plan Review Notes For Permit 04090203
Permit Number 04090203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-09-28 00:00:00************DENIED**********************
  
 1) PLEASE PROVIDE CUT SHEETS FOR FIRE
 ALARM PANEL AND ALL FIRE ALARM DEVICES
  
 2) REVISE NOTE # 10 FIRE ALARM SYSTEM
 SHALL BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 3) REVISE NOTE # 11 FIRE ALARM SYSTEM
 SHALL BE CLASS "A" OR FULLY ADDRESSABLE.
  
 4) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND A DOCUMENT
 ATTESTING TO THIS CERTIFICATION SHALL BE
 PROVIDE TO THE WEST PALM BEACH FIRE DEPT
 PRIOR TO FINAL APPROVAL OF THE
 INSTALLATION ON SITE.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722