| Plan Review Notes For Permit 04090203 |
| Permit Number |
04090203 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-28 00:00:00 | ************DENIED********************** | | | | | | 1) PLEASE PROVIDE CUT SHEETS FOR FIRE | | | ALARM PANEL AND ALL FIRE ALARM DEVICES | | | | | | 2) REVISE NOTE # 10 FIRE ALARM SYSTEM | | | SHALL BE UL LISTED FOR CENTRAL STATION | | | SERVICE. | | | | | | 3) REVISE NOTE # 11 FIRE ALARM SYSTEM | | | SHALL BE CLASS "A" OR FULLY ADDRESSABLE. | | | | | | 4) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND A DOCUMENT | | | ATTESTING TO THIS CERTIFICATION SHALL BE | | | PROVIDE TO THE WEST PALM BEACH FIRE DEPT | | | PRIOR TO FINAL APPROVAL OF THE | | | INSTALLATION ON SITE. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|