| Plan Review Notes For Permit 04090170 |
| Permit Number |
04090170 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-06 00:00:00 | *********DENIED************************* | | | | | | 1) PLEASE SUBMIT SHOP DRAWINGS AND CUT | | | SHEETS SHOWING LOCATION OF THE FACP. | | | | | | 2) WHEN THE FIRE ALARM CONTROL UNIT, | | | INCLUDING THE DIALER-COMMUNICATOR, IS | | | REPLACED IN AN EXISTING SYSTEM, IT WILL | | | BE TREATED AS IF IT WERE A NEW SYSTEM. | | | | | | 3) IS THIS BUILDING FIRE SPRINKLER | | | PROTECTED? PLEASE BE AWARE THAT ALL NEW | | | FIRE ALARM SYSTEMS THAT SUPERVISE FIRE | | | SPRINKLER SYSTEMS SHALL BE UL | | | CERTIFICATED AND HAVE DOCUMENT ATTESTING | | | TO THIS CERTIFICATION PRIOR TO FINAL | | | APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 4) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|