| 2006-03-24 00:00:00 | | | | THE GENERATOR ADDED TO THE RISER DIAGRAM | | | MUST BE APPLIED FOR ON A SEPARATE | | | PERMIT. | | | | | | THE REQUIREMENTS FOR A RESIDENTIAL | | | GENERATOR PERMIT APPLICATIION ARE IN THE | | | PACKAGE. | | | | | | AFTER THE GENERATOR PERMIT IS ISSUED THE | | | RISER FOR THESE PLANS WILL HAVE TO BE | | | RESUBMITTED TO SHOW THE CHANGES. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE CIRCUIT NUMBERS AT THE DEVICES DO | | | NOT MATCH THE PANEL SCHEDULES. INDICATE | | | PANEL DESIGNATION WITH THE BRANCH | | | CIRCUIT NUMBER, EG: A-33, EM-2 ETC. | | | | | | 2} THE PANELS IN THE UTILITY ROOM ARE IN | | | VIOLATION OF 110.26 CLEARANCE | | | REQUIREMENTS. | | | | | | 3} A RECEPTACLE NEEDS TO BE ADDED IN THE | | | MASTER BEDROOM TO COMPLY WITH 210.52(A) | | | SINCE THE CLOSET HAS BEEN REMOVED. | | | | | | 4} THE TOTAL DEMAND OF THE TWO PANELS | | | EXCEEDS THE SIZE OF THE SERVICE AND | | | LEAVES NO ROOM FOR FUTURE EXPANSION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|