| 2004-10-08 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE LAUNDRY CIRCUIT MUST BE |
| | CALCULATED PER 220.16 (B), SEE CIRCUIT |
| | #6, 1500VA. |
| | |
| | 2} PLEASE SEE THAT KITCHEN COUNTERTOP |
| | RECEPTACLE SPACING DOES NOT APPEAR TO |
| | COMPLY WITH 210.11(C)(1) SPACING |
| | REQUIREMENTS. THE DISHWASHER RECEPTACLE |
| | WOULD NOT BE INCLUDED IN THE SPACING AS |
| | IT IS DEDICATED AND BELOW THE COUNTER, |
| | ADD ONE ABOVE. ALSO SEE REVIEWED PLAN |
| | FOR REDLINED AREAS. |
| | |
| | 3} PLEASE SHOW THE LOCATION OF THE NEW |
| | 200 AMP DISCONNECT ON THE PLAN. |
| | |
| | 4} THE LIGHTING AND SMOKE DETECTOR |
| | WIRING IN BEDROOMS MUST ALSO COMPLY |
| | WITH 210.12. THE TERM "RECEPTACLE" HAS |
| | BEEN REPLACED WITH "OUTLETS" IN THE |
| | 2002 NEC. BY DEFINITION ALL ELECTRICAL |
| | DEVICES WOULD BE INCLUDED UNDER THAT |
| | ARTICLE. |
| | |
| | 5} THE ARCHITECT MUST SIGN THE PLANS |
| | NOT RUBBER STAMP HIS NAME, PER |
| | 61G1-16.003 FLORIDA ADMINISTRATIVE |
| | CODE, AND IS ENFORCED BY THIS |
| | DEPARTMENT. DO NOT SUBMIT PLANS IN |
| | VIOLATION OF THIS ARTICLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |