| Plan Review Notes For Permit 04090106 |
| Permit Number |
04090106 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-01-06 00:00:00 | DENIED; | | | FROM PREVIOUS REVIEW; | | | 1.PER H/C CODE SEC. 11-4.1,3 (10) SHOW | | | CUP DISPENSOR ON FLOOR PLAN AND MAKE A | | | NOTE FOR DETAIL ON PAGE A-5 DRINKING | | | FOUNTAIN WITH CUP DISPENSOR. | | | 2.PAGE P-3 WATER RISER DIAGRAM. THE ONLY | | | FIXTURE REQUIRING SHOCK ARRESTORS IS THE | | | CLOTHES WASHER. SEE PLUMBING CODE SEC. | | | 604.9 SHOCK ARRESTORS TO BE INSTALLED | | | PER MANUFACTOR SPECIFICATIONS. SEE RED | | | LINE ON PAGE P-3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|