Plan Review Notes
Plan Review Notes For Permit 04090106
Permit Number 04090106
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) THE FOLLOWING INFORMATION SHALL BE
 SHOWN ON THE PLANS FOR MEN'S/WOMEN'S
 BATHROOMS & UNISEX TOILET ROOM. SHOW
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.
 18, 11-4.19, & 11-4.22 AND ALL SUBSECT-
 IONS. - CLEAR FLOOR SPACE 11-4.16.2, 11-
 4.18.3, 11-4.19.3, & 11-4.22.3. TURNING
 AREAS FOR EACH TOILET ROOM/BATHROOM PER
 11-4.22.3. HEIGHTS AND CLEARANCES FOR
 THE LAVS 11-4.19.2, EXPOSED PIPES AND
 SURFACES 11-4.19.4. LAVS SHALL BE 15" TO
 CENTER OF FIXTURE FROM WALL. - SHOWERS
 SHALL SHOW FOLLOWING INFORMATION, CONTR-
 OR HEIGHT, FIGURE 37, AND CURB INFORMAT-
 ION PER 11-4.21.7
 2) SUBMIT A DETAIL FOR DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS. - ALSO SHOW COMPLI-
 ANCE WITH SECTION 11-4.1.3(10)(A) PRO-
 VISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 3) SUBMIT A SANITARY AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE
 SIZES, AND ON THE WATER DIAGRAM SHOW ALL
 WATER HAMMER ARRESTORS REQUIRED BY SECT-
 ION 604.9 LOCATED NEAR THE FIXTURES NOT
 IN THE CEILING PER PDI-WH 201.
  
 REVIEW BY KEN STEVENS