| Notes |
| Date |
Text |
| 2004-10-01 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM REMODEL. | | | | | | 4) PLEASE INDICATE LOCATIONS OF ALL | | | ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTS. | | | | | | 5) MORE DETAILS REQUIRED ON TURNSTILES | | | NEAR MAIN ENTRY WAY. PLEASE SEE NFPA 101 | | | SECTION 7.2.1.11. | | | | | | 6) PLEASE PROVIDE A LIFE SAFETY PLAN | | | INDICATING EXITS, TRAVEL DISTANCES, AND | | | OCCUPANT LOADS. | | | | | | 7) HOW DO THE CARD SWIPE DEVICES | | | AFFECT EXITING. | | | | | | 8) DO THE EXISTING RAMPS HAVE HANDRAILS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|