Plan Review Notes
Plan Review Notes For Permit 04090106
Permit Number 04090106
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-22 00:00:00********* UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE(S).
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF NEW OR EXISTING EM/EXT LTS.
 PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS
 TO SHOW EM/ EXT LTS TO VERIFY LOCATIONS
 FOR COMPLIANCE.
  
 3)NOTE: PLEASE CLARIFY/SHOW LOCATION
 OF NEW OR EXISTING SIGN CIRCUIT.
 600.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]