Plan Review Notes For Permit 04090091
Permit Number 04090091
Review Stop B
Sequence Number 1
Notes
Date Text
2004-10-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090091
 ADD: 477 ROSEMARY AV# 187
 CONT: SLATER & SONS G C
 TEL: (561)315-9515
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) EMPLOYEES KITCHEN SINK SHALL COMPLY
 WITH FORWARD APPROACH,AND ALL SUB SEC-
 TIONS, CLEAR FLOOR SPACE.11-4-24
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 3) 11-4.2.2.DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE, (KICHEN SINK).
  
 4)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCESAT DOORS THAT ARE NOT
 AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 A) AT NEW HANDICAPED SHOWER.
 B) REAR ENTRANCE
  
 5) HANDICAPPED SHOWER MISSING DETAILS
 FOR SEAT 11-4.21.3.
  
 6) 11-4.35.2. DRESSING & FITTING ROOMS.
 SEE ALL SUBSECTIONS 1-5.CLEAR FLOOR
 SPACE, DOORS, BENCH & MIRROR.
  
 7) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) 61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 9) NEW HANDICAPPED SHOWER / DRESSING
 ROOM,(DRESSING ROOM):
 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 10) 1204.3 SHOWERS. SHOWER COMPARTMENTS
 SHALL HAVE FLOORS AND WALLS CONSTRUCTED
 OF SMOOTH, CORROSION RESISTANT AND NON-
 ABSORBENT WATER-RESISTANT MATERIALS TO A
 HEIGHT OF NOT LESS THAN 70" ABOVE THE
 COMPARTMENT FLOOR AT DRAIN.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026