| 2004-11-23 00:00:00 | DENIED: |
| | COMMENTS FROM PREVIOUS REVIEW NOT |
| | ADDRESSED: |
| | COMMENT #1 - ENERGY CALCULATIONS STILL |
| | INDICATE SINGLE FAMILY.THIS IS A |
| | MULTI-FAMILY STRUCTURE.RESPONSE |
| | INDICTES THE CALCS WERE REVISED, BUT |
| | THEY STILL INDICATE "SINGLE FAMILY, ONE |
| | UNIT". |
| | |
| | COMMENT #3 - SINGLE PERMIT FOR THREE |
| | BUILDINGS - PLEASE SEE COMMENT #1 BY |
| | JIM |
| | WITMER, BUILDING PLAN REVIEW. |
| | |
| | COMMENT #4 - BUILDING TYPE - RESPONSE |
| | INDICATES PLAN SHEET A-1 FOR THE |
| | BUILDING TYPE & GROUP.NO INDICATION |
| | OF |
| | TYPE V, VI ETC.SEE ALSO COMMENT #4 BY |
| | JIM WITMER. |
| | |
| | COMMENT #6 - RETURN AIR FROM THE MASTER |
| | BEDROOM.REVISED PLAN INDICATES AN 8", |
| | 6" AND 4" SUPPLY AIR DUCT INTO THE |
| | MASTER SUITE.THIS EQUALS A TOTAL OF |
| | 91 |
| | SQUARE INCHES. 10" RETURN EQUALS ON 78 |
| | SQUARE INCHES. |
| | |
| | COMMENT #9 - ACCESS FOR THE AHU LOCATED |
| | IN THE ATTIC SHALL BE IN ACCORDANCE |
| | WITH |
| | 2001 FBC CHAPTER 13 SUB-CHAPTER |
| | 610.1.ABC.3.5.2 - RESPONSE INDICATES |
| | DETAIL WAS ADDED TO SHEET A-9.NO |
| | DETAIL OF THE ATTIC ACCESS IS SHOWN ON |
| | A-9. |
| | |
| | PLEASE NOTE, A COPY OF THE ORIGINAL |
| | PLANS SHOULD BE SUBMITTED WITH THE |
| | CORRECTED SHEETS TO HELP EXPEDITE THE |
| | RESUBMITTAL PROCESS. |
| | |