Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-11-10 00:00:001) ELECTRONIC SWITCHES, CHAIN AND
 LOCK REQUIRED ON FIRE LINE
 BACKFLOW DEVICE.
  
 2) WHAT FIRE HYDRANTS ARE GOING
 TO BE UTILIZED FOR FIREFIGHTING
 AND TO SUPPLY THE FIRE DEPARTMENT
 CONNECTIONS.
  
 3) REQUIRED FIRE SPRINKLER SYSTEMS
 SHALL BE MONITORED BY A LICENSED
 UL LISTED ALARM COMPANY FOR
 CENTRAL STATION SERVICE.
  
 4) PORTABLE FIRE EXTINGUISHERS
 ARE REQUIRED. THESE DEVICES ARE
 USED AS FIRST AID APPLIANCES
 AND CAN BE USED PRIOR TO THE ACTIVATION
 OF THE REQUIRED AUTOMATIC FIRE
 SPRINKLER SYSTEMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910