| 2004-11-17 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | 1)NOTE: PLEASE SEE NOTES #1&2 FROM JIM |
| | WITMER BLDG PLAN REVIEW INREFERENCE TO |
| | PERMITS AND PERMITTING OF PROJECT. |
| | |
| | 2)NOTE: PLEASE SEE SERVICE RISER HAS NOW |
| | BEEN CHANGED. PLEASE SEE GROUNDING |
| | ELECTRODE CONDUCTOR HAS NOW BEEN |
| | DECREASED TO A #4?? |
| | PLEASE SEE 250.50,FOR MIN CONNECTION |
| | REQUIREMENTS. CWP ALSO (IF METAL) AND |
| | FOOTER STEEL. |
| | PLEASE SEE 250.66 FOR SIZING. 3/0? |
| | |
| | 3)NOTE: PLEASE SEE OLD RISER INDICATED |
| | SIZE OF METER CENTER, HOWEVER THERE IS |
| | NO INDICATION OF THIS ON RISER AT THIS |
| | TIME? 215.5 |
| | |
| | 4)NOTE: PLEASE SEE SD'S ARE REQUIRED IN |
| | THE IMMEDIATE VICINITY LEADING TO FLR |
| | ABOVE. NFPA-72 8-1.4.2 |
| | |
| | ** NEW COMMENT** |
| | |
| | 5)NOTE: PLEASE SEE KITCHEN COUNTERSPACE |
| | AND 210.52C1 FOR REQUIRED SPACING. |
| | PLEASE SEE ONE SET OF PLANS HAS THIS ARE |
| | OF CONCERN REDLINED. |
| | PLEASE SEE THAT AREAS SEPARATE BY SINKS |
| | AND THE LIKE SHALL BE CONSIDERED TO BE |
| | "NEW COUNTERSPACE" AND THE END OF |
| | COUNTER SHALL START OVER. GFI REQUIRED |
| | W/IN 2' OF THE END AND EVERY 4' |
| | THEREAFTER. |
| | 210.52C1-5 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |