Plan Review Notes
Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-17 00:00:00*********** UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE NOTES #1&2 FROM JIM
 WITMER BLDG PLAN REVIEW INREFERENCE TO
 PERMITS AND PERMITTING OF PROJECT.
  
 2)NOTE: PLEASE SEE SERVICE RISER HAS NOW
 BEEN CHANGED. PLEASE SEE GROUNDING
 ELECTRODE CONDUCTOR HAS NOW BEEN
 DECREASED TO A #4??
 PLEASE SEE 250.50,FOR MIN CONNECTION
 REQUIREMENTS. CWP ALSO (IF METAL) AND
 FOOTER STEEL.
 PLEASE SEE 250.66 FOR SIZING. 3/0?
  
 3)NOTE: PLEASE SEE OLD RISER INDICATED
 SIZE OF METER CENTER, HOWEVER THERE IS
 NO INDICATION OF THIS ON RISER AT THIS
 TIME? 215.5
  
 4)NOTE: PLEASE SEE SD'S ARE REQUIRED IN
 THE IMMEDIATE VICINITY LEADING TO FLR
 ABOVE. NFPA-72 8-1.4.2
  
 ** NEW COMMENT**
  
 5)NOTE: PLEASE SEE KITCHEN COUNTERSPACE
 AND 210.52C1 FOR REQUIRED SPACING.
 PLEASE SEE ONE SET OF PLANS HAS THIS ARE
 OF CONCERN REDLINED.
 PLEASE SEE THAT AREAS SEPARATE BY SINKS
 AND THE LIKE SHALL BE CONSIDERED TO BE
 "NEW COUNTERSPACE" AND THE END OF
 COUNTER SHALL START OVER. GFI REQUIRED
 W/IN 2' OF THE END AND EVERY 4'
 THEREAFTER.
 210.52C1-5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  