| Date |
Text |
| 2004-10-12 00:00:00 | DENIED: |
| | INSUFFICIENT INFORMATION FOR REVIEW. |
| | PLEASE PROVIDE THE FOLLOWING: |
| | |
| | 1.ENERGY CALCULATIONS INDICATE "SINGLE |
| | FAMILY".THIS IS CONSIDERED "MULTI |
| | FAMILY". |
| | |
| | 2.PLAN INDICATES FOUR UNITS PER |
| | BUILDING.ENERGY CALCUALTIONS DO NOT |
| | SPECIFY INTERIOR UNIT TO EXTERIOR UNIT. |
| | |
| | 3.PLEASE CLARIFY ARE THESE UNITS TO |
| | BE INDIVIDUALLY PERMITTED OR PERMITTED |
| | BY BUILDING?SHOULD UNITS BE PERMITTED |
| | INDIVIDUALLY, 2 COMPLETE SETS OF PLANS, |
| | ENERGY & MANUAL J CALCS ARE REQUIRED FOR |
| | EACH PERMIT APPLICATION. |
| | |
| | 4.INDICATE BUILDING TYPE.(TYPE V)? |
| | |
| | 5.MECHANICAL PLAN (M-1) INDICATES |
| | OUTSIDE AIR CALCULATIONS, PLEASE SEE |
| | TABLE 403.3 FOR REQUIRMENTS.INCLUDE |
| | ALSO THE KITCHEN & BATHROOMS AS LISTED |
| | ON TABLE 403.3. |
| | |
| | 6.RETURN AIR JUMPER FROM THE MASTER |
| | BEDROOM IS NOT SIZED PROPERLY.ALL AIR |
| | INTO THE MASTER SUITE IS TO BE INCLULDED |
| | |
| | 7.RETURN AIR JUMPER FROM BEDROOM 1 |
| | ON THE FIRST FLOOR DOES NOT INDICATE |
| | DUCT SIZE. |
| | |
| | 8.SUPPLY DUCT TO BEDROOM 2, NO DUCT |
| | SIZE INDICATED. |
| | |
| | 9.MECHANICAL PLAN INDICATES ATTIC |
| | ACCESS.PLEASE NOTE ACCESS SHALL BE |
| | LOCATED WITHIN 6 FT OF THE SERVICE PANEL |
| | AND SHALL COMPLY WITH 2001 FBC CHAPTER |
| | 13 SUB-CHAPTER 610.1.ABC.3.5.2. |
| | 10. PLEASE PROVIDE DETAIL OF DUCTWORK |
| | BETWEEN THE WOOD TRUSS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |